Parameters and firmware blocks
125
10.16
D2D CW USED
(see above)
Selects the source for the control word for drive-to-drive communication. By default, the source is
parameter
Value pointer: Group and index
10.17
START ENABLE
(see above)
Selects the source for the start enable signal. If the start enable signal is switched off, the drive will not
start or stops if the drive is running. 1 = Start enable.
Note:
This parameter cannot be changed while the drive is running.
Note
: Functionality of the Start enable signal is different from the Run enable signal.
Example:
External damper control application using Start enable and Run enable. Motor can start
only after the damper is fully open.
Bit pointer: Group, index and bit
Drive started
Start/Stop commands
(group 10)
Start enable signal (10.17)
Started (6.01 STATUS
WORD 1 bit 2)
Damper status
Run enable signal from the
damper end switch when the
damper is fully opened
(10.09)
Motor speed
Acceleration
time (25.03)
Deceleration
time (25.04)
Damper
opening
time
Damper
closing
time
Damper open
Damper
closed
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...