![ABB ACSM1 Series Manual Download Page 315](http://html.mh-extra.com/html/abb/acsm1-series/acsm1-series_manual_2326315.webp)
Fault tracing
315
0005
DC UNDERVOLTAGE
(0x3220)
Intermediate circuit DC voltage
is not sufficient due to missing
mains phase, blown fuse or
rectifier bridge internal fault.
Check mains supply and fuses.
0006
EARTH FAULT
(0x2330)
Programmable fault:
Drive has detected load
unbalance typically due to earth
fault in motor or motor cable.
Check that there are no power factor
correction capacitors or surge absorbers in
motor cable.
Check that there is no earth fault in motor or
motor cables:
- measure insulation resistances of motor and
motor cable.
If no earth fault can be detected, contact your
local ABB representative.
0007
FAN FAULT
(0xFF83)
Fan is not able to rotate freely or
fan is disconnected. Fan
operation is monitored by
measuring fan current.
Check fan operation and connection.
0008
IGBT OVERTEMP
(0x7184)
Drive temperature based on
thermal model has exceeded
internal fault limit.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against unit power.
0009
BC WIRING
(0x7111)
Braking resistor is missing,
damaged or there is a problem
in the resistor cabling.
Short circuit in the braking
chopper IGBT.
Ensure that the braking resistor is connected
and not damaged.
Replace the braking chopper.
0010
BC SHORT CIRCUIT
(0x7113)
Short circuit in the braking
chopper IGBT.
Ensure that the braking resistor is connected
and not damaged.
Replace the braking chopper.
0011
BC OVERHEAT
(0x7181)
Braking chopper IGBT
temperature has exceeded
internal fault limit.
Let chopper cool down.
Check for excessive ambient temperature.
Check for cooling fan failure.
Check for obstructions in the air flow.
Check the dimensioning and cooling of the
cabinet.
Check resistor overload protection function
settings, parameters
Check that braking cycle meets allowed
limits.
Check that drive supply AC voltage is not
excessive.
Code
Fault
(fieldbus code)
Cause
What to do
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...