Fault tracing
316
0012
BR OVERHEAT
(0x7112)
Braking resistor temperature
has exceeded fault limit defined
by parameter
.
Stop drive. Let resistor cool down.
Check resistor overload protection function
settings, parameters
Check fault limit setting, parameter
.
Check that braking cycle meets allowed
limits.
0013
CURR MEAS GAIN
(0x3183)
Difference between output
phase U2 and W2 current
measurement gain is too great.
Contact your local ABB representative.
0014
CABLE CROSS CON
(0x3181)
Programmable fault:
Incorrect input power and motor
cable connection (ie, input
power cable is connected to
drive motor connection).
Check input power connections. This fault
can be disabled after the drive has been
commissioned until the input power cable or
motor cable are disconnected again.
0015
SUPPLY PHASE
(0x3130)
Programmable fault:
Intermediate circuit DC voltage
is oscillating due to missing
input power line phase or blown
fuse.
Check input power line fuses.
Check for input power supply imbalance.
0016
MOTOR PHASE
(0x3182)
Programmable fault:
Motor circuit fault due to
missing motor connection (all
three phases are not
connected).
Connect motor cable.
Code
Fault
(fieldbus code)
Cause
What to do
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...