Parameters and firmware blocks
213
Group
55 COMMUNICATION TOOL
Settings for an RS-485 network implemented using optional JPC-01 Network
communication adapters. The network enables the use of a single PC or control
panel to control multiple drives.
For more information, see the
JPC-01 Network communication adapter User’s
manual
(3AUA0000072233).
55
55.01
MDB STATION ID
FW block: None
Defines the ID of the drive on the RS-485 network. Each drive must have a dedicated ID number.
1…247
ID number. For drives, use a number between 1 and 31. (DriveStudio
uses ID number 247.)
55.02
MDB BAUD RATE
FW block: None
Sets the baud rate on the network.
Note:
This parameter must be set to
if a control panel is used as the controlling device.
(0)
Auto
Baud rate is determined automatically. At start-up, and after a
communication break, the initial rate is 9600 baud.
(1)
9600
9600 baud.
(2)
19200
19200 baud.
(3)
38400
38400 baud.
(4)
57600
57600 baud.
55.03
MDB PARITY
FW block: None
Defines the use of parity bits. The same setting must be used in all on-line stations.
0…3
Number of parity bits.
• 0 = 8 none 1
• 1 = 8 none 2
• 2 = 8 even 1
• 3 = 8 odd 1
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...