Parameters and firmware blocks
154
Group
24 SPEED REF MOD
Settings for
• speed reference selection
• speed reference modification (scaling and inversion)
• constant speed and jogging references
• definition of absolute minimum speed reference.
Depending on user selection, either speed reference 1 or speed reference 2 is active
at a time.
Speed reference can be any of the following (in priority order):
• fault speed reference (in a control panel or PC tool communication break)
• local speed reference (from panel)
• fieldbus local reference
• jogging reference 1/2
• constant speed reference 1/2
• external speed reference.
Note:
Constant speed overrides external speed reference.
Speed reference is limited according to the set minimum and maximum speed
values and ramped and shaped according to the defined acceleration and
deceleration values. See parameter group
(page
).
3.01 SPEED REF1
3.02 SPEED REF2
ZERO
AI1
AI2
FBA REF1
FBA REF2
D2D REF1
D2D REF2
ENC1 SPEED
ENC2 SPEED
24.01 SPEED
REF1 SEL
ZERO
AI1
AI2
FBA REF1
FBA REF2
D2D REF1
D2D REF2
ENC1 SPEED
ENC2 SPEED
24.02 SPEED
REF2 SEL
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...