![ABB ACSM1 Series Manual Download Page 336](http://html.mh-extra.com/html/abb/acsm1-series/acsm1-series_manual_2326336.webp)
Standard function blocks
336
OR
(10012)
Illustration
Execution time
1.55 µs (when two inputs are used) + 0.60 µs (for every additional input). When all
inputs are used, the execution time is 19.55 µs.
Operation
The output (OUT) is 0, if all connected inputs (IN) are 0. Otherwise the output is 1.
Truth table:
The inputs can be inverted.
Inputs
The number of inputs (2…32) is selected by the user.
Input (IN1…IN32): Boolean
Outputs
Output (OUT): Boolean
ROL
(10013)
Illustration
Execution time
1.28 µs
Operation
Input bits (I) are rotated to the left by the number (N) of bits defined by BITCNT. The N
most significant bits (MSB) of the input are stored as the N least significant bits (LSB) of
the output.
Example: If BITCNT = 3
Inputs
The input data type is selected by the user.
Number of bits input (BITCNT): INT, DINT
Input (I): INT, DINT
OR
58
TLA1 1 msec
(1)
IN1
IN2
OUT
OUT(58)
IN1
IN2
OUT
0
0
0
0
1
1
1
0
1
1
1
1
ROL
(DINT)
59
TLA1 1 msec
(1)
BITCNT
I
O
O(59)
I
1 1 1 0 0 0 0 0 1 1 1 0 0 1 0 1 1 1 0 1 0 0 1 1 0 0 1 1 0 1 0 1
O
0 0 0 0 0 1 1 1 0 0 1 0 1 1 1 0 1 0 0 1 1 0 0 1 1 0 1 0 1 1 1 1
3 MSB
3 LSB
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...