Parameters and firmware blocks
133
Group
13 ANALOGUE INPUTS
Settings for the analogue inputs.
The drive offers two programmable analogue inputs, AI1 and AI2. Both inputs can be
used either as a voltage or a current input (-11…11 V or -22…22 mA). The input type
is selected with jumpers J1 and J2 respectively on the JCU Control Unit.
The inaccuracy of the analogue inputs is 1% of the full scale range and the
resolution is 11 bits (+ sign). The hardware filter time constant is approximately 0.25
ms.
Analogue inputs can be used as the source for speed and torque reference.
Analogue input supervision can be added with standard function blocks. See chapter
.
13
Firmware block:
AI1
(12)
Filters and scales the analogue input
AI1 signal and selects the AI1
supervision. Also shows the value of
the input.
Block outputs located in other
parameter groups
)
(page
)
13.01
AI1 FILT TIME
(see above)
Defines the filter time constant for analogue input AI1.
Note:
The signal is also filtered due to the signal interface hardware (approximately 0.25 ms time
constant). This cannot be changed by any parameter.
0…30 s
Filter time constant for AI1.
13.02
AI1 MAX
(see above)
Defines the maximum value for analogue input AI1. The type is selected with jumper J1 on the JCU
Control Unit.
-11…11 V / -22…22 mA
Maximum AI1 input value.
AI1
23
TLF7 2 msec
(6)
13.01 AI1 FILT TIME
[ 0.000 s ]
13.02 AI1 MAX
[ 10.000 mA ]
13.03 AI1 MIN
[ -10.000 mA ]
13.04 AI1 MAX SCALE
[ 1500.000 ]
13.05 AI1 MIN SCALE
[ -1500.000 ]
2.04 AI1
2.05 AI1 SCALED
63
%
100
T
t
Filtered signal
Unfiltered signal
O = I · (1 - e
-t/T
)
I = filter input (step)
O = filter output
t = time
T = filter time constant
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...