Fault tracing
324
0053
D2D COMM
(0x7520)
Programmable fault:
On the master drive: The drive
has not been replied to by an
activated follower for five
consecutive polling cycles.
Check that all drives that are polled
(parameters
and
) on the drive-to-
drive link are powered, properly connected to
the link, and have the correct node address.
Check the drive-to-drive link wiring.
On a follower drive: The drive
has not received new reference
1 and/or 2 for five consecutive
reference handling cycles.
Check the settings of parameters
drive.
Check the drive-to-drive link wiring.
0054
D2D BUF OVLOAD
(0x7520)
Programmable fault:
Transmission of drive-to-drive
references failed because of
message buffer overflow.
Contact your local ABB representative.
0055
TECH LIB
(0x6382)
Resettable fault generated by a
technology library.
Refer to the documentation of the technology
library.
0056
TECH LIB CRITICAL
(0x6382)
Permanent fault generated by a
technology library.
Refer to the documentation of the technology
library.
0057
FORCED TRIP
(0xFF90)
Generic Drive Communication
Profile trip command.
Check PLC status.
0058
FIELDBUS PAR ERROR
(0x6320)
The drive does not have a
functionality requested by PLC,
or requested functionality has
not been activated.
Check PLC programming.
Check fieldbus parameter settings. See
parameter group
on page
.
0059 STALL
(0x7121)
Programmable fault:
Motor is operating in stall region
because of, eg, excessive load
or insufficient motor power.
Check motor load and drive ratings.
Check fault function parameters.
0061
SPEED FEEDBACK
(0x8480)
No speed feedback is received.
Check the settings of the parameters in group
.
Check encoder installation. See the
description of fault
(ENCODER1) for
more information.
Check encoder cabling. See the descriptions
of faults
(ENCODER1) and
(ENCODER2) for more information.
0062
D2D SLOT COMM
(0x7584)
Drive-to-drive link is set to use
an FMBA module for
communication, but no module
is detected in specified slot.
Check the settings of parameters
and
that the FMBA module has been detected by
checking parameters
…
Check that the FMBA module is correctly
wired.
Try installing the FMBA module into another
slot. If the problem persists, contact your local
ABB representative.
Code
Fault
(fieldbus code)
Cause
What to do
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...