Parameters and firmware blocks
180
33.09
SUPERV3 FUNC
(see above)
Selects the mode of supervision 3.
(0)
Disabled
Supervision 3 not in use.
(1)
Low
When the signal selected by parameter
below the value of parameter
, bit 2 of
is activated. To clear the bit, the signal must
exceed the value of parameter
(2)
High
When the signal selected by parameter
exceeds the value of parameter
, bit 2 of
is activated. To clear the bit, the signal must fall
below the value of parameter
(3)
Abs Low
When the absolute value of the signal selected by parameter
falls below the value of parameter
is activated. To clear the bit,
the absolute value of the signal must exceed the value of parameter
(4)
Abs High
When the absolute value of the signal selected by parameter
exceeds the value of parameter
is activated. To clear the bit, the
absolute value of the signal must fall below the value of parameter
33.10
SUPERV3 ACT
(see above)
Selects the signal to be monitored by supervision 3. See parameter
Value pointer: Group and index
33.11
SUPERV3 LIM HI
(see above)
Sets the upper limit for supervision 3. See parameter
-32768…32768
Upper limit for supervision 3.
33.12
SUPERV3 LIM LO
(see above)
Sets the lower limit for supervision 3. See parameter
.
-32768…32768
Lower limit for supervision 3.
33.17
BIT0 INVERT SRC
FW block: None
Parameters 33.17...
enable the inversion of freely selectable source bits. The inverted bits are
shown by parameter
.
This parameter selects the source bit whose inverted value is shown by parameter
DI1
Digital input DI1 (as indicated by
DI2
Digital input DI2 (as indicated by
DI3
Digital input DI3 (as indicated by
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...