Standard function blocks
381
FIO_11_DIO_slot2
(10087)
Illustration
Execution time
6.0 µs
Operation
The block controls the two digital inputs/outputs (DIO1, DIO2) of a FIO-11 Digital I/O
Extension mounted on slot 2 of the drive control unit.
The state of a DIOx conf input of the block determines whether the corresponding DIO
on the FIO-11 is an input or an output (0 = input, 1 = output). If the DIO is an output, the
DOx input of the block defines its state.
The DIx outputs show the state of the DIOs.
The DIx filt gain inputs determine a filtering time for each input as follows:
Inputs
Digital input/output mode selection (DIO1 conf, DIO2 conf): Boolean
Digital output state selection (DO1, DO2): Boolean
Digital input filter gain selection (DI1 filt gain, DI2 filt gain): INT
Outputs
Digital input/output state (DI1, DI2): Boolean
Error output (Error): DINT (0 = No error; 1 = Application program memory full)
FIO_11_DIO_slot2
56
TLA1 1 msec
(1)
DIO1 conf
DIO2 conf
DO1
DO2
DI1 filt gain
DI2 filt gain
DI1
DI1(56)
DI2
DI2(56)
Error
Error(56)
DIx filt gain
Filtering time
0
7.5 µs
1
195 µs
2
780 µs
3
4.680 ms
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...