Parameters and firmware blocks
245
67.01
SYNC REF SEL
(see above)
Selects the source for the position reference in synchron control.
(0)
ZERO
Zero position reference.
(1)
AI1
Analogue input 1.
(2)
AI2
Analogue input 2.
(3)
FBA REF1
Fieldbus reference 1.
(4)
FBA REF2
Fieldbus reference 2.
(5)
D2D REF1
Drive-to-drive reference 1.
(6)
D2D REF2
Drive-to-drive reference 2.
(7)
Reserved.
(8)
POS 2ND ENC
Encoder 2.
(9)
VIRT MAST
Virtual master reference selected by parameter
67.02
VIRT MAS REF SEL
(see above)
Selects the source for the virtual master speed reference.
(0)
ZERO
Zero position reference.
(1)
AI1
Analogue input 1.
(2)
AI2
Analogue input 2.
(3)
FBA REF1
Fieldbus reference 1.
(4)
FBA REF2
Fieldbus reference 2.
(5)
D2D REF1
Drive-to-drive reference 1.
(6)
D2D REF2
Drive-to-drive reference 2.
(7)
ENC1 SPEED
Encoder 1.
(8)
ENC2 SPEED
Encoder 2.
(9)
VM SPD REF
Parameter
.
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...