Parameters and firmware blocks
198
46.06
SUPPL PHS LOSS
(see above)
Selects how the drive reacts when a supply phase loss is detected. This parameter is only used with
an AC supply.
(0)
No
No reaction.
(1)
Fault
Drive trips on SUPPLY PHASE fault.
46.07
STO DIAGNOSTIC
(see above)
Selects how the drive reacts when it detects the absence of one or both Safe Torque Off (STO)
signals.
Note:
This parameter is for supervision only. The Safe Torque Off function can activate even when
this parameter is set to
For general information on the Safe Torque Off function, see the
Hardware Manual
of the drive and
Application guide - Safe torque off function for ACSM1, ACS850 and ACQ810 drives
(3AFE68929814
[English]).
(1)
Fault
The drive trips on SAFE TORQUE OFF when one or both of the STO
signals are lost.
(2)
Alarm
Drive running:
The drive trips on SAFE TORQUE OFF when one or both of the STO
signals is lost.
Drive stopped:
The drive generates a SAFE TORQUE OFF alarm if both STO signals
are absent. If only one of the signals is lost, the drive trips on STO1
LOST or STO2 LOST.
(3)
No
Drive running:
The drive trips on SAFE TORQUE OFF when one or both of the STO
signals is lost.
Drive stopped:
No action if both STO signals are absent. If only one of the signals is
lost, the drive trips on STO1 LOST or STO2 LOST.
(4)
Only Alarm
The drive generates a SAFE TORQUE OFF alarm if both STO signals
are absent. If only one of the signals is lost, the drive trips on STO1
LOST or STO2 LOST.
46.08
CROSS CONNECTION
(see above)
Selects how the drive reacts to incorrect input power and motor cable connection (ie, input power
cable is connected to drive motor connection). This parameter is only used with an AC supply.
(0)
No
No reaction.
(1)
Fault
Drive trips on CABLE CROSS CON fault.
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...