Standard function blocks
376
The AIx filt gain inputs determine a filtering time for each input as follows:
The AIx mode outputs show whether the corresponding input is voltage (0) or current
(1). The voltage/current selection is made using the hardware switches on the FIO-11.
Inputs
Analogue input filter gain selection (AI1 filt gain … AI3 filt gain): INT
Minimum value of input signal (AI1 Min … AI3 Min): REAL (> -11 V or -22 mA)
Maximum value of input signal (AI1 Max … AI3 Max): REAL (< 11 V or 22 mA)
Minimum value of scaled output signal (AI1 Min scale … AI3 Min scale): REAL
Maximum value of scaled output signal (AI1 Max scale … AI3 Max scale): REAL
Outputs
Analogue input mode (voltage or current) (AI1 mode … AI3 mode): Boolean
Value of analogue input (AI1 … AI3): REAL
Scaled value of analogue input (AI1 scaled … AI3 scaled): REAL
Error output (Error): DINT (0 = No error; 1 = Application program memory full)
AIx scaled
32768
AIx [V or mA]
11 V or
-11 V or
AIx
Max
AIx M
in
AIx Min Scale
AIx Max Scale
-22 mA
22 mA
AIx Min Scale > AIx Max Scale
-32768
AIx filt gain
Filtering time
Notes
0
No filtering
1
125 µs
Recommended setting
2
250 µs
3
500 µs
4
1 ms
5
2 ms
6
4 ms
7
7.9375 ms
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...