Fault tracing
323
0047
MOTOR OVERTEMP
(0x4310)
Programmable fault:
Estimated motor temperature
(based on motor thermal model)
has exceeded fault limit defined
by parameter
.
Check motor ratings and load.
Let motor cool down. Ensure proper motor
cooling: Check cooling fan, clean cooling
surfaces, etc.
Check value of fault limit.
Check motor thermal model settings,
parameters
and
.
Measured motor temperature
has exceeded fault limit defined
by parameter
.
Check that actual number of sensors
corresponds to value set by parameter
Check motor ratings and load.
Let motor cool down. Ensure proper motor
cooling: Check cooling fan, clean cooling
surfaces, etc.
Check value of fault limit.
Broken wire in the temperature
sensor.
Check the temperature sensor connection.
0048
POS ACT MEASURE
(0x8584)
Selected operation mode
requires position feedback data
(actual position), but no
feedback data is available.
Check actual position source setting,
Check encoder installation. See ENCODER1
fault description for more information.
(The used operation mode is indicated by
signal
.)
0049
AI SUPERVISION
(0x8110)
Programmable fault:
Analogue input AI1 or AI2 signal
has reached limit defined by
parameter
Check analogue input AI1/2 source and
connections.
Check analogue input AI1/2 minimum and
maximum limit settings, parameters
and
and
0050
ENCODER 1 CABLE
(0x7389)
Programmable fault:
Encoder 1 cable fault detected.
Check cable between FEN-xx interface and
encoder 1. After any modifications in cabling,
re-configure interface by switching drive
power off and on, or by activating parameter
0051
ENCODER 2 CABLE
(0x738A)
Programmable fault:
Encoder 2 cable fault detected.
Check cable between FEN-xx interface and
encoder 2. After any modifications in cabling,
re-configure interface by switching drive
power off and on, or by activating parameter
0052
D2D CONFIG
(0x7583)
Configuration of the drive-to-
drive link has failed for a reason
other than those indicated by
alarm
, for example start
inhibition is requested but not
granted.
Contact your local ABB representative.
Code
Fault
(fieldbus code)
Cause
What to do
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...