Parameters and firmware blocks
136
(3)
AI2 min tune
Current analogue input AI2 signal value is set as minimum value for
AI2, parameter
automatically.
(4)
AI2 max tune
Current analogue input AI2 signal value is set as maximum value for
AI2, parameter
. The value reverts back to
automatically.
13.12
AI SUPERVISION
FW block: None
Selects how the drive reacts when analogue input signal limit is reached. The limit is selected by
parameter
(0)
No
No action taken.
(1)
Fault
The drive trips on fault AI SUPERVISION.
(2)
Spd ref Safe
The drive generates alarm AI SUPERVISION and sets the speed to
the speed defined by parameter
.
WARNING!
Make sure that it is safe to continue operation in
case of a communication break.
(3)
Last speed
The drive generates alarm AI SUPERVISION and freezes the speed
to the level the drive was operating at. The speed is determined by the
average speed over the previous 10 seconds.
WARNING!
Make sure that it is safe to continue operation in
case of a communication break.
13.13
AI SUPERVIS ACT
FW block: None
Selects the analogue input signal supervision limit.
Example: If parameter value is set to 0010 (bin), bit 1 AI1>max is selected.
0b0000…0b1111
AI1/AI2 signal supervision selection.
Bit
Supervision selected by parameter
AI SUPERVISION is activated if
0
AI1<min
AI1 signal value falls below the value defined by equation:
par.
1
AI1>max
AI1 signal value exceeds the value defined by equation:
par.
+ 0.5 mA or V
2
AI2<min
AI2 signal value falls below the value defined by equation:
par.
3
AI2>max
AI2 signal value exceeds the value defined by equation:
par.
+ 0.5 mA or V
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...