Parameters and firmware blocks
193
(1)
KTY JCU
The temperature is supervised using a KTY84 sensor connected to
drive thermistor input TH.
(2)
KTY 1st FEN
The temperature is supervised using a KTY84 sensor connected to
encoder interface module FEN-xx installed in drive Slot 1/2. If two
encoder interface modules are used, encoder module connected to
Slot 1 is used for the temperature supervision.
Note:
This selection
does not apply for FEN-01. *
(3)
KTY 2nd FEN
The temperature is supervised using a KTY84 sensor connected to
encoder interface module FEN-xx installed in drive Slot 1/2. If two
encoder interface modules are used, encoder module connected to
Slot 2 is used for the temperature supervision.
Note:
This selection
does not apply for FEN-01. *
(4)
PTC JCU
The temperature is supervised using 1…3 PTC sensors connected to
drive thermistor input TH.
(5)
PTC 1st FEN
The temperature is supervised using 1…3 PTC sensors connected to
encoder interface module FEN-xx installed in drive Slot 1/2. If two
encoder interface modules are used, encoder module connected to
Slot 1 is used for the temperature supervision. *
(6)
PTC 2nd FEN
The temperature is supervised using 1…3 PTC sensors connected to
encoder interface module FEN-xx installed in drive Slot 1/2. If two
encoder interface modules are used, encoder module connected to
Slot 2 is used for the temperature supervision. *
*Note:
If one FEN-xx module is used, parameter setting must be either
. The FEN-xx module can be in either Slot 1 or Slot 2.
45.03
MOT TEMP ALM LIM
(see above)
Defines the alarm limit for the motor overtemperature protection (when par.
=
or
).
0…200 °C
Motor overtemperature alarm limit.
45.04
MOT TEMP FLT LIM
(see above)
Defines the fault limit for the motor overtemperature protection (when par.
MOT TEMP PROT =
0…200 °C
Motor overtemperature fault limit.
45.05
AMBIENT TEMP
(see above)
Defines the ambient temperature for the thermal protection mode.
-60…100 °C
Ambient temperature.
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...