Fault tracing
318
0019
CURR V2 MEAS
(0x3185)
Measured offset error of V2
output phase current
measurement is too great.
(Offset value is updated during
current calibration.)
Contact your local ABB representative.
0020
CURR W2 MEAS
(0x3186)
Measured offset error of W2
output phase current
measurement is too great.
(Offset value is updated during
current calibration.)
Contact your local ABB representative.
0021
STO1 LOST
(0x8182)
Safe Torque Off function is
active, i.e. safety circuit signal 1
connected between X6:1 and
X6:3 is lost while drive is at
stopped state and parameter
setting is
or
.
Check safety circuit connections. For more
information, see the appropriate drive
hardware manual and
Application guide -
Safe torque off function for ACSM1, ACS850
and ACQ810 drives
(3AFE68929814
[English]).
0022
STO2 LOST
(0x8183)
Safe Torque Off function is
active, i.e. safety circuit signal 2
connected between X6:2 and
X6:4 is lost while drive is at
stopped state and parameter
setting is
or
.
Check safety circuit connections. For more
information, see the appropriate drive
hardware manual and
Application guide -
Safe torque off function for ACSM1, ACS850
and ACQ810 drives
(3AFE68929814
[English]).
0024
INTBOARD OVERTEMP
(0x7182)
Interface board (between power
unit and control unit)
temperature has exceeded
internal fault limit.
Let drive cool down.
Check for excessive ambient temperature.
Check for cooling fan failure.
Check for obstructions in the air flow.
Check the dimensioning and cooling of the
cabinet.
0025
BC MOD OVERTEMP
(0x7183)
Input bridge or braking chopper
temperature has exceeded
internal fault limit.
Let drive cool down.
Check for excessive ambient temperature.
Check for cooling fan failure.
Check for obstructions in the air flow.
Check the dimensioning and cooling of the
cabinet.
Code
Fault
(fieldbus code)
Cause
What to do
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...