ZP1-X3E Series Operation 
Manual 

P/N 501-419503-2-10 • REV 01 • ISS 17MAR14 

Summary of Contents for ZP1-X3E Series

Page 1: ...ZP1 X3E Series Operation Manual P N 501 419503 2 10 REV 01 ISS 17MAR14...

Page 2: ...other relevant provisions of Directive 1999 5 EC 2002 96 EC WEEE directive Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union For proper recycling...

Page 3: ...ity ii Introduction 1 Control panel overview 3 The user interface 3 Operator controls and indicators 4 Audible indicators 11 Control panel status indications 11 Control panel operation 18 User levels...

Page 4: ...any lost profits or business opportunities loss of use business interruption loss of data or any other indirect special incidental or consequential damages under any theory of liability whether based...

Page 5: ...ons for a single extinguishing area If a fire detection zone is not configured as part of the extinguishing detection area the control panel provides standard fire panel functionality for that fire de...

Page 6: ...alarm state or a start extinguishing manual call point was pressed In this state extinguishing sounders are activated Normally your system installer will have configured an intermittent tone If the ex...

Page 7: ...g Fault LED 12 Reserved for future use 13 Expansion I O Fault Disabled LED 14 General Disable button and LED 15 General Test button and LED 16 Low Pressure LEDs 17 Extinguishing Agent Flow LEDs 18 Res...

Page 8: ...1 Zone buttons and LEDs Z1 Z2 Z3 Red Yellow Disables or tests a zone when pressed with the General Disable or General Test button A red LED indicates a fire alarm in the corresponding zone A flashing...

Page 9: ...that the actuator has been activated and the control panel is waiting confirmation of the release of the extinguishing agent flow Consult your system installer to determine whether your system has th...

Page 10: ...es a safety door monitoring fault or disablement Safety door monitoring is optional A fast flashing LED indicates a safety door open or closed faulty status as follows When the control panel is not in...

Page 11: ...ment 15 General Test button and LED Yellow Tests a system feature or device when pressed with the corresponding button Testing of some devices requires pressing the button for more than 3 seconds See...

Page 12: ...ounders If the LED is off pressing the button activates the fire sounders if the control panel status and operating mode allow manual activation of sounders The LED also indicates the status of the so...

Page 13: ...ady yellow LED indicates that there is no mains power and the battery power is insufficient A flashing yellow LED indicates that the mains power is insufficient and there is no battery power 25 Earth...

Page 14: ...A flashing yellow LED indicates an open or short circuit wiring fault A steady yellow LED indicates a disablement or test 30 Fire Routing Delay button and LED Yellow Enables or disables a previously...

Page 15: ...LED if a delay is enabled A steady Fire Routing Delay LED Figure 1 item 30 if a delay is enabled There is no audible indication Fire alarm fire only The fire alarm state applies to zones that are not...

Page 16: ...the system is configured so that a second zone in the extinguishing area is required to activate the extinguishing event Extinguishing event conditions are detected one or two zones go into fire alar...

Page 17: ...is in this state when In automatic mode the extinguishing event conditions are detected one or two zones go into fire alarm depending on the system configuration The start manual call point is presse...

Page 18: ...MCP Hold is deactivated the delay countdown determines when the panel enters the extinguishing activation state In Mode A activation of the MCP Hold turns on the MCP Hold LED which stays on until the...

Page 19: ...n as usual if the extinguishing event that caused the release was not a start manual call point activation Fire routing indications if configured are shown in the usual manner linked to the fire alarm...

Page 20: ...shing switches are indicated by a steady General Disable LED and a steady yellow LED for Disable extinguishing switch There is no audible indication For BS 7273 mode the buzzer is intermittent when th...

Page 21: ...state there are no further fire alarm or fault signals from detection zones and no activation deactivaton or fault signals from input devices are processed The out of service state is indicated as fo...

Page 22: ...sword security To enter the operator user level enter the password using the numeric keypad and then press Enter A long beep and a steady Reset LED indicate that the correct password was entered and t...

Page 23: ...ated by a manual call point overrides any configured delay and activates the fire sounders immediately Cancelling an active fire routing delay If a fire routing delay is enabled and active press the F...

Page 24: ...est fire routing Disable or enable a zone Test a zone Disable or enable the extinguishing event Disable other extinguishing devices Test other extinguishing devices Set the manual only mode of operati...

Page 25: ...activation by pressing the Fire Sounders Start Stop button During the time from the end of the configured disable time period until the end of the configured fire sounder delay when the Fire Sounders...

Page 26: ...lt if there is an alarm Note Disabling the extinguishing sounders automatically prevents disables the extinguishing event See Disabling or enabling the extinguishing event on page 25 for more informat...

Page 27: ...Disable button and then press the Fire Routing Start button The disablement is indicated as follows A steady General Disable LED A steady yellow Fire Routing On LED To enable fire routing press the G...

Page 28: ...button The test is indicated as follows A steady General Test LED A steady fault disable test Zone LED When an alarm is activated in a zone in test The alarm Zone LED is steady or flashing depending...

Page 29: ...n prevent or disable the extinguishing event See Extinguishing event prevented on page 13 for more details Disabling other extinguishing devices The devices listed in Table 4 can also be disabled at t...

Page 30: ...e corresponding device To exit from a test condition press the General Test button for more than 3 seconds press the 1 and 3 buttons to select the option and then press Enter Table 5 Additional input...

Page 31: ...irm the test command the primary actuator output is activated immediately Set the manual only mode of operation If the control panel is not configured to use an external input to switch to manual only...

Page 32: ...f the system This inspection must test at least one device per zone and verify that the control panel responds to all fault and alarm events The control panel power supply and battery voltage should b...

Page 33: ...ection Type C only 8 3 Fault signals from points 8 4 Total loss of power supply 10 Test condition 1 Inputs and outputs on the optional 2010 1 SB expansion board do not support the optional requirement...

Page 34: ...nufacturing representative UTC Fire Security B V Kelvinstraat 7 6003 DH Weert The Netherlands Year of first CE marking 13 Declaration of Performance number 360 3117 2199 EN 54 EN 54 2 1997 AC 1999 A1...

Page 35: ......

Page 36: ......