Страница 3: ...1 CAN page 49 1 3 2 SSC page 49 1 3 3 RS232 page 49 1 3 4 LON page 49 2 General page 50 2 1 Keys page 50 2 1 1 Function keys page 50 2 1 2 Cursor movement keys page 50 2 1 3 Home key page 51 2 1 4 Edi...

Страница 4: ...Temperature sensors page 64 4 6 3 Wind sensors page 64 4 6 4 Wind direction sensor page 65 4 7 Functions page 65 4 7 1 Tilting function page 65 4 7 2 Sun function page 67 4 7 3 Temperature function p...

Страница 5: ...oned as VBC gives access to a lot of information like the measured sensor values state of functions and a logfile It also gives access to a lot of control possibilities like manual operation automatic...

Страница 6: ...tom and fix the device to the wall with 4 screws The drill distances are shown below The second option is to use the 2 spacers These can be used to create a distance of 11 mm between the wall and the...

Страница 7: ...llowed to combine both 230 V and 24 V on the outputs In that case use external relayboxes The group outputs 10 33 are split up in blocks of 4 relays or 2 groups Each block has its own common The commo...

Страница 8: ...ee picture must be placed to the left For sensor 2 jumper 2 see picture must be placed to the left Current sensor with heating more than 100 mA The sensor cannot be directly powered by the VBC Therefo...

Страница 9: ...ust be placed to the left side Digital sensor with our without heating Both with and without heating can be directly connected to the VBC provided that the heating consumes no more then 100 mA Connect...

Страница 10: ...onnect more inputs to one keyswitch 1 2 9 Rain sensor The rain sensor is connected with 6 wires The connections on the rain sensor 1 6 cor respond with connections 170 175 on the VBC With the 2 DIP sw...

Страница 11: ...S232 The RS232 interface can be used for maintenance and visualization There are two options to connect the cable use a male 9 pin SUB D connector or directly connect the cable to the 5 terminals Neve...

Страница 12: ...eys The functionality of the function key will be described by the area left to the function key This could be plain text or a pictogram When the area left to the function key is blank that means ther...

Страница 13: ...Main area o Shows the current menu When a scrollbar is visible to the right of the main area means that the current menu has some items which are not visible The size of the shutter repre sents the vi...

Страница 14: ...menu section sensors 52 Picture 2 Menu main The main menu is the most upper menu From this main menu the user can select a number of sub menus To select another sub menu use the cursor control keys UP...

Страница 15: ...to the priority an icon is shown which represents the function Below a description of all func tions with their associated icon Next to the function type the state of the function will be shown Below...

Страница 16: ...Next group Show detailed description of next group Previous group Show detailed description of previous group 3 3 3 Active function overview This function shows an overview of the active functions fo...

Страница 17: ...l be the window cleaning function When looking at the active function overview this will be confirmed 3 4 Control Picture 6 Menu control by hand function Picture 7 Menu control by sun function The con...

Страница 18: ...Switch to control by hand function This function key is only available when control by sun function is selected 3 4 4 Screen layout The main area is divided into two sections The layout has much simi...

Страница 19: ...57 Picture 8 Menu configuration enter Within the configuration menu a lot of settings can be made For this reason the menu is password pro tected For a detailed description of the configura tion menu...

Страница 20: ...he Vestalon module will be shown Version Software version Date Software release date Name Vestalon id name Neuron ID Vestalon neuron id Project Project name description Contact info Contact informatio...

Страница 21: ...be inserted When entering a password characters entered will be showed as The function keys have the following functionality Move the cursor within the edited text to the left Move the cursor within...

Страница 22: ...nsaver is enabled the timeout can be set from 1 to 60 minutes When for the timeout time no key is pressed the backlight will go off When pressing a key again the backlight will go on the key pressed w...

Страница 23: ...clock stops ticking till the new time and date will be saved At the bottom of the main area the new time and date will be show 4 3 2 Set date The menu set date shows the default current date see pictu...

Страница 24: ...eering up can be extended Normally steering the sun shade down goes faster than steering the same sunshade up This will be caused by the earth gravity When setting up extra to 15 means that the runtim...

Страница 25: ...Sonnensensoren Global settings Unit The unit of the sun sensor can only be set to klx Maybe that in the future the unit type for the sun sensor will be extended Sensor n settings Enabled Enable or dis...

Страница 26: ...gs Enabled Enable or disable sensor n Alias A description for sensor n 4 6 3 Wind sensors Global settings Unit The unit of the wind sensors can be set to m s metres per second km h kilometres per hour...

Страница 27: ...sor n 4 7 Functions In the next paragraphs the configuration of the different functions will be explained 4 7 1 Tilting function 65 Picture 23 Menu wind direction sensor Picture 24 Menu tilting functi...

Страница 28: ...tilting parameter For example figure 24 menu tilting function month january The first period of time of the daily tilting function starts at 9 00 o clock with a tilting posi tion of 50 This position...

Страница 29: ...s active The sun high threshold must always be above the low threshold Assigned sensors Sensor Gives a list of all possible sensors which can be assigned to this function When moving the cursor over t...

Страница 30: ...the temperature threshold Set when the temperature function will become active Active When below The temperature function will become active when the actual temperature is below the programmed thresh...

Страница 31: ...sensors Sensor Gives a list of all possible sensors which can be assigned to this function When moving the cursor over the different sensor indexes the alias will show the corresponding name of that...

Страница 32: ...t sensor When assigning more than one sensor to this function the highest meas ured value of the assigned sensors will be used Alias When the cursor is on a sensor index the alias shows the correspond...

Страница 33: ...alse no rain the function becomes inactive 4 7 7 Window cleaning function Global settings Group Group selection Alias Shows the alias of the current selected group Enabled Enable or disable the window...

Страница 34: ...he function conditions stay true external input UP DOWN active the function becomes active Inactive delay Set the function inactive time in seconds When during this time the function conditions stay f...

Страница 35: ...e none fixed or during the day 4 7 10 Fire function Global settings Group Group selection Alias Shows the alias of the current selected group Enabled Enable or disable the fire function Function Activ...

Страница 36: ...Set the command action to perform when this time slot becomes active The command action can be UP or DOWN Type Set the command type running or continuously Blocking Enable or disable the blocking rela...

Страница 37: ...sor connection The message Wind sensor xx defect appears Bad connection or short circuit Jumper J1 J2 in wrong position Check wind sensor connection and jumper placement chapter 1 2 3 The message Wind...