Standard function blocks
404
Timers
MONO
(10057)
Illustration
Execution time
1.46 µs
Operation
The output (O) is set to 1 and the timer is started, if the input (I) is set to 1. The output is
reset to 0 when the time defined by the time pulse input (TP) has elapsed. Elapsed time
(TE) count starts when the output is set to 1 and stops when the output is set to 0.
If RTG is 0, a new input pulse during the time defined by TP has no effect on the
function. The function can be restarted only after the time defined by TP has elapsed.
If RTG is 1, a new input pulse during the time defined by TP restarts the timer and sets
the elapsed time (TE) to 0.
Example 1: MONO is not re-triggable, i.e. RTG = 0.
Example 2: MONO is re-triggable, i.e. RTG = 1.
Inputs
Re-trigger input (RTG): Boolean
Time pulse input (TP): DINT (1 =
µs)
Input (I): Boolean
Outputs
Output (O): Boolean
Time elapsed output (TE): DINT (1 = 1 µs)
MONO
85
TLA1 1 msec
(1)
RTG
TP
I
O
O(85)
TE
TE(85)
I
O
RTG = 0, TP = 4 s
0
1
t / s
2
3
4
5
6
7
8
9
10
4 s
4 s
TE = 0 s
TE = 4 s
TE = 0 s
TE = 4 s
TE = 0 s
I
O
RTG = 1, TP = 2 s
0
1
t / s
2
3
4
5
6
7
8
9
10
2 s
TE = 0 s
TE = 2 s
* TE is set to 0.
*
*
*
*
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...