Parameters and firmware blocks
135
13.07
AI2 MAX
(see above)
Defines the maximum value for analogue input AI2. The type is selected with jumper J2 on the JCU
Control Unit.
-11…11 V / -22…22 mA
Maximum AI2 input value.
13.08
AI2 MIN
(see above)
Defines the minimum value for analogue input AI2. The type is selected with jumper J2 on the JCU
Control Unit.
-11…11 V / -22…22 mA
Minimum AI2 input value.
13.09
AI2 MAX SCALE
(see above)
Defines the real value that corresponds to the maximum analogue input value defined by parameter
-32768…32768
Real value corresponding to value of parameter
13.10
AI2 MIN SCALE
(see above)
Defines the real value that corresponds to the minimum analogue input value defined by parameter
. See parameter
.
-32768…32768
Real value corresponding to value of parameter
13.11
AITUNE
FW block: None
Triggers the AI tuning function.
Connect the signal to the input and select the appropriate tuning function.
(0)
No action
AI tune is not activated.
(1)
AI1 min tune
Current analogue input AI1 signal value is set as minimum value for
AI1, parameter
. The value reverts back to
automatically.
(2)
AI1 max tune
Current analogue input AI1 signal value is set as maximum value for
AI1, parameter
automatically.
AI
(scaled)
AI
(mA / V)
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...