Automatic identification of the supply voltage is performed every time the drive is
powered. Automatic identification can be disabled by parameter
; the user can define the voltage manually at parameter
.
The intermediate DC circuit is charged over an internal resistor which is bypassed
when the capacitors are considered charged and the voltage has stabilized.
Braking chopper
The built-in braking chopper of the drive can be used to handle the energy generated
by a decelerating motor.
When the braking chopper is enabled and a resistor connected, the chopper will start
conducting when the DC link voltage of the drive reaches
U
DC_BR
- 30 V. The
maximum braking power is achieved at
U
DC_BR
+ 30 V.
U
DC_BR
= 1.35 × 1.25 ×
Low voltage mode
A Low voltage mode is available to extend the supply voltage range. When the mode
is enabled, the drive can operate below the nominal range, for example when it
needs to be powered from an emergency supply.
Low voltage mode can be activated by parameter
voltage mode introduces parameters
for adjustment of minimum and maximum DC voltage control levels
respectively. The following rules apply:
•
= 250 to 450 V
•
= 350 to 810 V
•
+ 50 V.
Undervoltage control level (0.8 ×
U
DC
; 400 V min.)
Undervoltage trip level (
U
DC
, low - 50 V; 350 V min.)
Overvoltage control level (1.25 ×
U
DC
; 810 V max.)
Overvoltage fault level (
U
DC
, high + 70 V; 880 V max.)
U
DC
U
DC
, high = 1.25 ×
U
DC
U
DC
, low = 0.8 ×
U
DC
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...