541
In This Chapter
Maximum Ambient Operating Temperature........................................... 540
Serial RS-232 "DB9" Port Pinouts .......................................................... 540
Serial RS-232 "RJ-45" Port Pinouts (for iX7™ Only)............................... 541
Sensor RJ-45 Port Pinouts...................................................................... 541
Feature RJ-45 Port Pinouts .................................................................... 542
Expansion RJ-45 Port Pinouts (for iX7™ Only) ....................................... 542
Maximum Ambient Operating Temperature
The maximum ambient operating temperature (TMA) for PX3 varies from
50 to 60 degrees Celsius, depending on the model and certification
standard (CE or UL). If necessary, contact Raritan Technical Support for
this information for your model.
Specification
Measure
Max Ambient Temperature
50 to 60 degrees Celsius
Serial RS-232 "DB9" Port Pinouts
RS-232 Pin/signal definition
Pin No.
Signal
Direction
Description
1 DCD
Input
Data
2
RxD
Input
Receive data (data in)
3 TxD
Output
Transmit
data
4
DTR
Output
Data terminal ready
5 GND
― Signal
ground
6
DSR
Input
Data set ready
7
RTS
Output
Request to send
8
CTS
Input
Clear to send
9 RI Input
Ring
indicator
Appendix A Specifications
Содержание PX3-1000 series
Страница 5: ......
Страница 92: ...Chapter 4 Connecting External Equipment Optional 70...
Страница 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Страница 669: ...Appendix J RADIUS Configuration Illustration 647 10 Select Standard to the left of the dialog and then click Add...
Страница 670: ...Appendix J RADIUS Configuration Illustration 648 11 Select Filter Id from the list of attributes and click Add...
Страница 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Страница 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...
Страница 722: ...Appendix L Integration 700 3 Click OK...