Chapter 3: Initial Installation and Configuration
52
The following restrictions do NOT apply to the other PDU that does not
have the door handles connected.
When there are 4 or 3 handles connected to the PDU (via a maximum
of two DX-PD2C5 packages), "only one" additional DPX/DPX2/DPX3
environmental sensor package can be connected to that PDU.
Raritan's sensor hubs must NOT be used.
When there are 2 handles connected to the PDU (via only one
DX-PD2C5), up to 10 sensor packages of DPX/DPX2/DPX3 or up to 2
additional DX sensor packages can be additionally connected.
Raritan's sensor hubs must NOT be used.
When there is only 1 handle connected, up to 12 sensor packages of
DPX/DPX2/DPX3 or up to 3 DX sensor packages can be additionally
connected. Raritan's sensor hubs must NOT be used.
NO physical changes made to the number of connected sensor
packages:
When either PDU enters the power-sharing mode, you must NOT
physically remove or add environmental sensor packages to BOTH
PDUs.
Warning: The in-rush current of a newly added sensor package may
cause both PDUs to reboot.
For information on Raritan's sensor packages or hubs, see
Connecting
Environmental Sensor Packages
(on page 53).
Содержание PX3-1000 series
Страница 5: ......
Страница 92: ...Chapter 4 Connecting External Equipment Optional 70...
Страница 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Страница 669: ...Appendix J RADIUS Configuration Illustration 647 10 Select Standard to the left of the dialog and then click Add...
Страница 670: ...Appendix J RADIUS Configuration Illustration 648 11 Select Filter Id from the list of attributes and click Add...
Страница 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Страница 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...
Страница 722: ...Appendix L Integration 700 3 Click OK...