Chapter 4: Connecting External Equipment (Optional)
56
2.
Connect DPX sensor packages to any of the four OUT ports on the
hub.
This diagram illustrates a configuration with a sensor hub connected.
The PX3 device
RJ-12 to RJ-45 adapter
Raritan-provided phone cable
DPX-ENVHUB4 sensor hub
DPX sensor packages
Using an Optional DPX-ENVHUB2 cable
A Raritan
DPX-ENVHUB2 cable doubles the number of connected
environmental sensors per SENSOR port.
This cable supports DPX sensor packages only. Do NOT connect DPX2,
DPX3 or DX sensor packages to it.
To connect DPX sensor packages via the DPX-ENVHUB2 cable:
1.
Use an RJ-12 to RJ-45 adapter to connect the DPX-ENVHUB2 cable
to the PX3.
a.
Connect the adapter's RJ-12 connector to the cable.
b.
Connect the adapter's RJ-45 connector to the RJ-45 SENSOR
port on the PX3.