Chapter 8: Using the Command Line Interface
406
Setting the Outlet Relay Behavior
This section applies to outlet-switching capable models only.
This command syntax determines the relay behavior of all outlets on a
PX3 model.
config:#
pdu relayBehaviorOnPowerLoss <option>
Variables:
<option> is one of the options:
latching or nonLatching.
Note: For more information on the outlet relay behavior, see
PX3
Latching Relay Behavior
(on page 150).
Setting the Outlet Power-On Sequence
This section applies to outlet-switching capable models only.
This command sets the outlet power-on sequence when the PDU powers
up.
config:#
pdu outletSequence <option>
Variables:
<option> is one of the options:
default, or a comma-separated list of
outlet numbers.
Option
Description
default
All outlets are switched ON in the ASCENDING
order (from outlet 1 to the final outlet) when the
PX3 device powers up.
A comma-
separated list
of outlet
numbers
All outlets are switched ON in the order you
specify using the comma-separated list.
The list must include all outlets on the PDU.
Note: Power-on sequencing is disabled in the latching mode. See
PX3
Latching Relay Behavior
(on page 150).
Содержание PX3-1000 series
Страница 5: ......
Страница 92: ...Chapter 4 Connecting External Equipment Optional 70...
Страница 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Страница 669: ...Appendix J RADIUS Configuration Illustration 647 10 Select Standard to the left of the dialog and then click Add...
Страница 670: ...Appendix J RADIUS Configuration Illustration 648 11 Select Filter Id from the list of attributes and click Add...
Страница 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Страница 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...
Страница 722: ...Appendix L Integration 700 3 Click OK...