Appendix F: PX3 Models with Residual Current Monitoring
602
Running RCM Self-Test
You can perform RCM self-test for a specific inlet via CLI. After the
self-test finishes, the test result is shown: pass or fail.
To perform RCM self-test:
#
rcm selfTest inlet <n>
Variables:
<n> is the inlet's number. For a single-inlet PDU, <n> is always 1.
Degaussing RCM Type B Sensors
Only the models with RCM 'Type B' sensors support degaussing the RCM
sensors. Those with RCM Type A sensors do NOT support this feature.
You can degauss the RCM sensor after a current surge, such as a short
circuit.
To degauss RCM Type B sensors:
#
rcm degauss