Chapter 4: Connecting External Equipment (Optional)
84
The beeper can be located at a distance up to 330 feet (100 m) away
from the PX3.
Connecting a Schroff LHX/SHX Heat Exchanger
To remotely monitor and administer the Schroff
®
LHX-20, LHX-40 and
SHX-30 heat exchangers through the PX3 device, you must establish a
connection between the heat exchanger and the PX3 device.
For more information on the LHX/SHX heat exchanger, see the user
documentation accompanying that product.
To establish a connection between the PDU and LHX/SHX heat exchanger,
an RJ-45 to RS-232 adapter cable provided by Schroff is required.
To connect an LHX or SHX heat exchanger:
1.
Plug the RS-232 DB9 end of the adapter cable into the RS-232 port
on the Schroff LHX/SHX heat exchanger.
2.
Plug the RJ-45 end of the cable into the port labeled FEATURE on
your PX3 device.
To enable the support of the LHX/SHX heat exchanger, see
Miscellaneous
(on page 332).
Содержание PX3-1000 series
Страница 5: ......
Страница 92: ...Chapter 4 Connecting External Equipment Optional 70...
Страница 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Страница 669: ...Appendix J RADIUS Configuration Illustration 647 10 Select Standard to the left of the dialog and then click Add...
Страница 670: ...Appendix J RADIUS Configuration Illustration 648 11 Select Filter Id from the list of attributes and click Add...
Страница 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Страница 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...
Страница 722: ...Appendix L Integration 700 3 Click OK...