Chapter 8: Using the Command Line Interface
504
config:#
sensor inlet 1 current upperWarning 20 lowerWarning 12
Results:
The Upper Warning threshold for the inlet 1 RMS current is set to
20A. It also enables the upper warning threshold if this threshold has
not been enabled yet.
The Lower Warning threshold for the inlet 1 RMS current is set to
12A. It also enables the lower warning threshold if this threshold has
not been enabled yet.
Example 3 - Upper Thresholds for Overcurrent Protector Sensors
The following command sets both the Upper Critical and Upper Warning
thresholds for the 2nd overcurrent protector.
config:#
sensor ocp 2 current upperWarning enable upperCritical 16
Results:
The Upper Critical threshold for the 2nd overcurrent protector's
RMS current is set to 16A. It also enables the upper critical threshold
if this threshold has not been enabled yet.
The Upper Warning threshold for the 2nd overcurrent protector's
RMS current is enabled.
Содержание PX3-1000 series
Страница 5: ......
Страница 92: ...Chapter 4 Connecting External Equipment Optional 70...
Страница 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Страница 669: ...Appendix J RADIUS Configuration Illustration 647 10 Select Standard to the left of the dialog and then click Add...
Страница 670: ...Appendix J RADIUS Configuration Illustration 648 11 Select Filter Id from the list of attributes and click Add...
Страница 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Страница 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...
Страница 722: ...Appendix L Integration 700 3 Click OK...