![Raritan PX3-1000 series Скачать руководство пользователя страница 298](http://html1.mh-extra.com/html/raritan/px3-1000-series/px3-1000-series_user-manual_3780217298.webp)
Chapter 6: Using the Web Interface
276
Radio buttons for different events:
According to the event you select, the "Trigger condition" field containing
three radio buttons may or may not appear.
Event types
Radio buttons
Numeric sensor
threshold-crossing
events, or the
occurrence of the
selected event --
true or false
Available radio buttons include "Asserted,"
"Deasserted" and "Both."
Asserted: The PX3 takes the action only
when the selected event occurs. That is, the
status of the event transits from FALSE to
TRUE.
Deasserted: The PX3 takes the action only
when the selected event disappears or
stops. That is, the status of the selected
event transits from TRUE to FALSE.
Both: The PX3 takes the action both when
the event occurs (asserts) and when the
event stops/disappears (deasserts).
State sensor state
change
Available radio buttons include
"Alarmed/Open/On," "No longer
alarmed/Closed/Off" and "Both."
Alarmed/Open/On: The PX3 takes the action
only when the chosen sensor enters the
alarmed, open or on state.
No longer alarmed/Closed/Off: The PX3
takes the action only when the chosen
sensor returns to the normal, closed, or off
state.
Both: The PX3 takes the action whenever the
chosen sensor switches its state.
Sensor availability
Available radio buttons include "Unavailable,"
"Available" and "Both."
Unavailable: The PX3 takes the action only
when the chosen sensor is NOT detected and
becomes unavailable.
Available: The PX3 takes the action only
when the chosen sensor is detected and
becomes available.
Both: The PX3 takes the action both when
the chosen sensor becomes unavailable or
available.
Содержание PX3-1000 series
Страница 5: ......
Страница 92: ...Chapter 4 Connecting External Equipment Optional 70...
Страница 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Страница 669: ...Appendix J RADIUS Configuration Illustration 647 10 Select Standard to the left of the dialog and then click Add...
Страница 670: ...Appendix J RADIUS Configuration Illustration 648 11 Select Filter Id from the list of attributes and click Add...
Страница 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Страница 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...
Страница 722: ...Appendix L Integration 700 3 Click OK...