Chapter 3: Initial Installation and Configuration
44
Number
Device role
Slave 2
Slave 3
To cascade iX7
™
PDUs via Ethernet ports:
1.
Make sure all Raritan devices to be cascaded are running firmware
version 3.3.10 or later.
2.
Choose one iX7
™
PDU as the master device.
3.
Log in to all devices one by one and select the same cascading mode.
See
Setting the Cascading Mode
(on page 231).
Bridging mode:
Set the cascading mode of all devices to Bridging.
Port Forwarding mode:
Set the cascading mode of all devices to Port Forwarding. Make
sure the cascading role and downstream interface are also set
correctly.
4.
Connect the master device to the LAN, using a method below.
Bridging mode: Use a standard network patch cable (CAT5e or
higher).
Port Forwarding mode: Use a standard network patch cable or a
Raritan USB WIFI wireless LAN adapter. For information on the
Raritan USB WIFI adapter, see
USB Wireless LAN Adapters
(on
page 25).
5.
Connect the available Ethernet port of the master device to either
Ethernet port of another iX7
™
via a standard network patch cable.
This additional iX7
™
device is Slave 1.
6.
Connect Slave 1's available Ethernet port to either Ethernet port of
another iX7
™
via a standard network patch cable. The second
additional device is Slave 2.
7.
Repeat the same step to connect more iX7
™
devices.
8.
Configure or change the network settings of the master and/or slave
devices as needed.
Bridging: Each cascaded device has its own network settings. For
example, some devices can have DHCP-assigned IP and the
others can have static IP addresses.
Port forwarding: Only the master device's network settings
should be configured.
Содержание PX3-1000 series
Страница 5: ......
Страница 92: ...Chapter 4 Connecting External Equipment Optional 70...
Страница 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Страница 669: ...Appendix J RADIUS Configuration Illustration 647 10 Select Standard to the left of the dialog and then click Add...
Страница 670: ...Appendix J RADIUS Configuration Illustration 648 11 Select Filter Id from the list of attributes and click Add...
Страница 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Страница 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...
Страница 722: ...Appendix L Integration 700 3 Click OK...