Request LHX/SHX Maximum Cooling
If Schroff LHX/SHX Support is enabled, the LHX/SHX-related actions will
be available. See
Miscellaneous
(on page 332).
The "Request LHX/SHX Maximum Cooling" action applies the maximum
cooling to the SHX-30 device only. The LHX-20 and LHX-40 devices do not
support this feature.
In the maximum cooling mode, an SHX-30 device runs at 100% fan speed
and the cold water valve is open 100%.
Operation:
1.
Choose Device Settings > Event Rules >
.
2.
Select "Request LHX/SHX Maximum Cooling" from the Action list.
3.
In the Available LHX/SHX field, select the desired SHX-30 device one
by one, or click Select All.
4.
To remove any SHX-30 device from the Selected LHX/SHX field, click
that device's
or click Deselect All.
Send Email
You can configure emails to be sent when an event occurs and can
customize the message.
Messages consist of a combination of free text and PX3 placeholders.
The placeholders represent information is pulled from the PX3 and
inserted into the message.
For example:
[USERNAME] logged into the device on [TIMESTAMP]
translates to
JQPublic logged into the device on 2012-January-30 21:00
For a list and definition of available variables, see
Email and SMS
Message Placeholders
(on page 309).
Operation:
1.
Choose Device Settings > Event Rules >
.
2.
Select "Send email" from the Action list.
3.
In the "Recipient Email Addresses" field, specify the email
address(es) of the recipient(s). Use a comma to separate multiple
email addresses.
4.
To use the SMTP server specified on the SMTP Server page, make
sure the "Use custom SMTP Server" checkbox is NOT selected.
Содержание PX3-1000 series
Страница 5: ......
Страница 92: ...Chapter 4 Connecting External Equipment Optional 70...
Страница 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Страница 669: ...Appendix J RADIUS Configuration Illustration 647 10 Select Standard to the left of the dialog and then click Add...
Страница 670: ...Appendix J RADIUS Configuration Illustration 648 11 Select Filter Id from the list of attributes and click Add...
Страница 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Страница 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...
Страница 722: ...Appendix L Integration 700 3 Click OK...