Chapter 8: Using the Command Line Interface
411
Specifying the Device Altitude
This command specifies your PX3 device's altitude above sea level (in
meters). You must specify the PX3 device's altitude above sea level if a
Raritan's DPX differential air pressure sensor is attached. This is
because the device's altitude is associated with the altitude correction
factor. See
Altitude Correction Factors
(on page 684).
config:#
pdu deviceAltitude <altitude>
Variables:
<altitude> is an integer between 1 and 3000 meters.
Setting the Z Coordinate Format for Environmental Sensors
This command enables or disables the use of rack units for specifying
the height (Z coordinate) of environmental sensors.
config:#
pdu externalSensorsZCoordinateFormat <option>
Variables:
<option> is one of the options:
rackUnits or freeForm.
Option
Description
rackUnits
The height of the Z coordinate is measured in
standard rack units. When this is selected, you
can type a numeric value in the rack unit to
describe the Z coordinate of any environmental
sensors or actuators.
freeForm
Any alphanumeric string can be used for
specifying the Z coordinate.
Note: After determining the format for the Z coordinate, you can set a
value for it. See
Setting the Z Coordinate
(on page 489).
Содержание PX3-1000 series
Страница 5: ......
Страница 92: ...Chapter 4 Connecting External Equipment Optional 70...
Страница 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Страница 669: ...Appendix J RADIUS Configuration Illustration 647 10 Select Standard to the left of the dialog and then click Add...
Страница 670: ...Appendix J RADIUS Configuration Illustration 648 11 Select Filter Id from the list of attributes and click Add...
Страница 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Страница 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...
Страница 722: ...Appendix L Integration 700 3 Click OK...