Appendix K: Additional PX3 Information
687
L2 = 5.2 amps
L3 = 4.0 amps
Average current: (5.5+5.2+4.0) / 3 = 4.9 amps
L1 current unbalance: (5.5 - 4.9) / 4.9 = 0.1224
L2 current unbalance: (5.2 - 4.9) / 4.9 = 0.0612
L3 current unbalance: (4.0 - 4.9) / 4.9 = -0.1837
Maximum current unbalance:
Maximum (|0.1224|, |0.0612|, |-0.1837|) = 0.1837
Current unbalance converted to a percentage:
100 * (0.1837) = 18%
Data for BTU Calculation
The heat generated by the PX3 device differs according to the model you
purchased. To calculate the heat (BTU/hr), use the following power data
according to your model type in the BTU calculation formula.
Model name
Maximum power (Watt)
PX2-1000
PX3-1000
5
PX2-2000
PX3-2000
20
PX2-3000
PX3-3000
24
PX2-4000
PX3-4000
24
PX2-5000
PX3-5000
24
Содержание PX3-1000 series
Страница 5: ......
Страница 92: ...Chapter 4 Connecting External Equipment Optional 70...
Страница 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Страница 669: ...Appendix J RADIUS Configuration Illustration 647 10 Select Standard to the left of the dialog and then click Add...
Страница 670: ...Appendix J RADIUS Configuration Illustration 648 11 Select Filter Id from the list of attributes and click Add...
Страница 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Страница 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...
Страница 722: ...Appendix L Integration 700 3 Click OK...