Appendix K: Additional PX3 Information
685
The PDView shows a "Connected" message when it detects the
physical connection to the PX3.
4.
Log in to the PDView app at the login prompt. Now you can view
limited PX3 information or even change some settings.
Tip: To skip the final login step, you can click the upper right icon of
PDView to save one or multiple user credentials. Next time the app
automatically logs in when it detects the PX3.
Altitude Correction Factors
If a Raritan differential air pressure sensor is attached to your device,
the altitude you enter for the device can serve as an altitude correction
factor. That is, the reading of the differential air pressure sensor will be
multiplied by the correction factor to get a correct reading.
This table shows the relationship between different altitudes and
correction factors.
Altitude (meters)
Altitude (feet)
Correction factor
0 0 0.95
250 820 0.98