manualshive.com logo in svg
background image

 

1

 

www.fiduspower.com

  

 

MVPS800 

Series

  

 

Dimensions:

 

5 x 8.5 x 

1.61” (127 

x 216 x 40.9mm)

 

Parameter

 

Minimum

 

Typical

 

Maximum

 

Units

 

Notes & Conditions

 

AC Input range

 

85

 

 

264

 

VAC

 

Derate from 100% at 120VAC to 70% at 85VAC

 

Operating temperature

 

-

40

 

 

70

 

°C

 

See derating curve p3. 

 

Efficiency

 

120VAC 88% and 240VAC 93% typical

 

Dimensions

 

5 x 8.5 x 

1.61” (127 

x 216 x 40.9mm)

 

EMC

 

EN55011 Level B conducted and radiated with king core K5B RC 25x12x15

-

M on input.  EN61000

-

3 and EN61000

-

4, harmonics, 

flicker, Surge, EFT, ESD, conducted and radiated immunity IEC 60601

-

1

-

2 4th Ed

 

Safety

 

EN60601

-

1, IEC6061

-

1 (ed3), ANSI/AMMI ES 60601

-

1, CSA C22.2 No 60601

-

1

 

Key specifications

 

• 

5 x 

8.5” 

Footprint, 

1.61” 

for 1U installation 

 

• 

Latest medical approvals IEC 60601

-

1 (3.1) IEC 60601

-

1

-

2 (4th)

 

• 

Up to 3 units load share for higher powers 

 

• 

Peak of 1000W for 500mS

 

• 

EN55011 Level B conducted & radiated

 

• 

3 Year warranty

 

 

800 Watts

 

The MVPS800 series of low profile, medically approved AC

-

DC power modules offer 300

-

800W in a 

5” 

8.5” 

package conforming to the latest IEC60601

-

1 3.1 and IEC60601

-

1

-

2 4th ed standards. The 

units are fully featured including 5V 1.5A auxiliary output and low standby power of 3W. The units are 
body floating (BF) rated for applied part applications. They have a wide operating temperature of –

40 

to 70°C, in a range of voltages from 12V to 58V. All units come with a FiDUS 3 year warranty.

 

Notes  

 

2.  Combined output power is main DC  fan output 12V / 500mA max

 

1.  For slotted cover change 

above for 

S

, for solid cover version change 

0

 above for 

T

 

3.  1000W overload for 500mS for 30V 48V and 58V only, not field configurable.

 

Model Number 

(1)  

 

Output 

Voltage 

 

Output Current  

 

Output   

Power

(2) 

 

U Channel            

Convection

 

U Channel         

with 300 LFM 

 

Slotted Cover   

Convection

 

Slotted Cover          

with 300 LFM

 

Solid Cover          

Convection

 

Solid Cover          

with 300 LFM

 

MVPS800

-

1

0

12

 

12V

 

25A

 

33.33A

 

17.5A

 

31.25A

 

15A

 

31.25A

 

180

-

400W

 

MVPS800

-

1

0

15

 

15V

 

25A

 

33.33A

 

17.5A

 

31.25A

 

15A

 

31.25A

 

225

-

500W

 

MVPS800

-

1

0

24

 

24V

 

25A

 

33.33A

 

17.5A

 

31.25A

 

15A

 

31.25A

 

360

-

800W

 

MVPS800

-

1

0

30

 

30V

 

20A

 

26.66A

 

14A

 

25A

 

12A

 

25A

 

360

-

800W

 

MVPS800

-

1

0

48

 

48V

 

12.5A

 

16.66A

 

8.75A

 

15.625A

 

7.5A

 

15.625A

 

360

-

800W

 

MVPS800

-

1

0

58

 

58V

 

10.34A

 

13.78A

 

7.25A

 

12.93A

 

6.2A

 

12.93A

 

360

-

800W

 

Models & Ratings

 

INSTALLATION ADVICE PG6

 

Содержание MVPS800 Series

Страница 1: ...test IEC60601 1 3 1 and IEC60601 1 2 4th ed standards The units are fully featured including 5V 1 5A auxiliary output and low standby power of 3W The units are body floating BF rated for applied part applications They have a wide operating temperature of 40 to 70 C in a range of voltages from 12V to 58V All units come with a FiDUS 3 year warranty Notes 2 Combined output power is main DC output fan...

Страница 2: ...ation Input to Output 4245 VAC Input to Ground 1625 VAC Output to ground 1500 VAC Switching frequency 85 100 kHz 100 kHz variable for power switching Variable PFC switching 85kHz Power density 11 69 W In3 MTBF 1 28 MHrs As per Telcordia SR332 issue 3 Weight 1100 g General Parameter Minimum Typical Maximum Units Notes Conditions Operating temperature 40 70 C Please see derating curve on page 3 Stor...

Страница 3: ...ptions EN61000 4 11 100 for 0 5 1 cycle 30 for 25 cycles B B B interrupt 250 300 cycles and 30 for 30 cycles B B B EMC Immunity WLP350 Series VPS800 Series MVPS800 Series 300LFM FAN COOLED 40 20 0 20 40 60 Temperature ᵒC 80 400 50 30 167 334 40 20 0 20 40 60 Temperature ᵒC 80 500 300 Load W 50 30 209 418 40 20 0 20 40 60 Temperature ᵒC 80 800 Load W 50 30 312 200 400 100 200 400 666 600 375 156 U ...

Страница 4: ... the units With other units tuned off on each PSU use the output adjust to change Vout within 1 The current share should be checked with a DC hall sensor showing that the power supplies share the current within 10 Signals Power Good TTL output activated at 90 of Vout Delay between 100 and 500mS At least 1mS before Vout falls below 90 TTL signal switches low Remote Sense Compensation for 200mV volt...

Страница 5: ...ept AMP 8 31886 1 Tongue 11A max AWG16 J3 I O Connector 4 Pin Connections Pin Function 1 GND 2 5V 1 5A 3 PGPF 4 VS 5 VS 6 GND 7 Remote on off 8 Current limit p2 9 Current limit p1 10 Load share ULP275 Series WLP350 Series 4 J3 I O header Molex 22 23 2101 mating part Molex 22 01 2107 MVPS600 Series J1 Input Connector 2 Pin Connections Pin Function 1 Line 2 Neutral 3 Earth U Channel Slotted cover So...

Страница 6: ...n some power supplies there may be additional earth tags or mounting points 2 Minimise the length of input output wiring where possible and try to maintain max distance of the conductors from the PSU to prevent noise pick up Avoid bundling input and output cables together A common component to avoid placing wiring near is the PFC inductor in power factor corrected power supplies 3 Apply additional...

Отзывы: