Appendix G: Old PX3 Character LCD Display
620
2.
Verify the LCD is showing the inlet's current, which is indicated by
the presence of the letter "A." If not, switch to current by pressing
the FUNC button.
3.
Depending on the type of your PX3, the procedure to display the
residual current slightly differs.
Single-phase PDU: Press the Up or Down button until the word
"LEAK" displays.
3-phase PDU: Press the Up button until the word "LEAK"
displays.
Below illustrates the residual current information shown on the LCD
display.
Section
Example information
The inlet containing RCM sensor is INLET 1.
This residual current is 0 mA.
ALARM always displays for residual current sensor.
LEAK always displays for residual current sensor.
Measurement units are mA.
To run RCM self-test:
1.
Press the MODE button until the LCD alternates between "SLF" and
"tSt," which means SELF TEST.
2.
Press the FUNC button to start RCM self-test.
3.
The LCD shows dash symbols during RCM self-test.
4.
Upon completion, RCM self-test results are displayed for 30 seconds,
or until you press any button.
PAS: Self-test passed.
FAL: Self-test failed (the PX3 also beeps).
Содержание PX3-1000 series
Страница 5: ......
Страница 92: ...Chapter 4 Connecting External Equipment Optional 70...
Страница 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Страница 669: ...Appendix J RADIUS Configuration Illustration 647 10 Select Standard to the left of the dialog and then click Add...
Страница 670: ...Appendix J RADIUS Configuration Illustration 648 11 Select Filter Id from the list of attributes and click Add...
Страница 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Страница 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...
Страница 722: ...Appendix L Integration 700 3 Click OK...