Montage- und Bedienungsanleitung
Assembly and operating instructions
Notice de montage et d’emploi

PDR/PDM

PDR/PDM

PDR/PDM

7857.300 

7857.310 

7857.320 

Содержание 7857.300

Страница 1: ...Montage und Bedienungsanleitung Assembly and operating instructions Notice de montage et d emploi PDR PDM PDR PDM PDR PDM 7857 300 7857 310 7857 320 ...

Страница 2: ...n 10 8 Technical specifications 8 1 PDR 11 8 2 PDM 11 9 Functions 9 1 PDR 12 9 2 PDM 12 10 Installation 10 1 Installing the PDR 13 10 2 Installing the PDM 14 10 3 Installing the PDR infeed 15 10 4 Installing the PDM in the PDR 16 11 Commissioning 11 1 PDR 17 11 2 PDM 17 12 Operation 12 1 PDR 18 12 2 PDM 18 13 Notes on maintenance 18 14 Cleaning 19 15 Disposal 19 16 Warranty 20 17 Customer service a...

Страница 3: ...r door frame 䡲 Rear panel 䡲 Side panels and roof plate 䡲 Levelling feet incl base plinth adaptor 䡲 Earthing of all enclosure panels 䡲 Busbars touch protected 䡲 Integral master switch Power Distribution Module PDM 䡲 482 6 mm 19 module 3 U 䡲 Incl master switch 䡲 4 fused 3 phase outlets to the rack 䡲 3 x 230 V 16 A per outlet 䡲 Connection cables 400 V 3 phase max 63 A F Power Distribution Rack PDR 䡲 ...

Страница 4: ...hnique suffisante pour le montage l instal lation sur site et le raccordement d armoires électriques selon les normes électriques électroniques mécaniques et pneumatiques en vigueur La notice d utilisation s adresse aux opérateurs et aux spécialistes formés pour la maintenance électrotechnique 2 1 Certification CE La déclaration de conformité peut être téléchargée depuis le site Internet de Rittal ...

Страница 5: ...e expansion is easy by means of Power Distribution Modules PDM Power Distribution Rack PDR and Power Distribution Module PDM provide a revolutionary energy management for IT racks The modular power supply system allows for energy supply from the 250 A infeed through up to 8 plug in Power Distribution Modules PDM The PDR is destined exclusively for operation in the data centre The significant featur...

Страница 6: ... completed in a few easy steps When system require ments increase the Power Distribution Module PDM can simply be expanded The Power Distribution Rack PDR and Power Distribu tion Module PDM represent a revolutionary approach to IT rack energy management The modular power supply system enables energy to be supplied from the 250 A infeed via up to 8 Power Distribution Modules PDM that can be plugged...

Страница 7: ...ner Lådorna måste säkras under transport montering och installation så att de inte kan välta Uso conforme campi di applicazione I lavori sull impianto elettrico devono essere ese guiti esclusivamente da una persona avvertita PAV o persona esperta PES in conformità alla norma EN 50110 Questo prodotto può essere utilizzato esclusivamente come accessorio per la fornitura e la distribuzione di energia...

Страница 8: ...i és műszaki termek Ettől eltérő alkalmazás esetén a Rittal lal kell konzultálni A termékek kizárólag a Rittal által előírt rendszertartozékkal kombinálhatók és üzemeltethetők Biztonsági tudnivalók A szekrényeket szállítás fel és kiépítés során feldőlés ellen biztosítani kell Naudojimas pagal paskirtį naudojimo sritys Darbus su elektros įrenginiais turi atlikti tik kvalifikuotas elektrikas pagal EN...

Страница 9: ... werden Dies ist über die separat erhältliche PDM Anschlussleitung zu realisie ren Die PDM Anschlussleitung hat die Best Nr 7857 351 Bitte Vorsicherung beachten Siehe Hinweise auf dem Typenschild Die Kabelabfangung und sicherung erfolgt mittels beiliegendem Kabelbügel am einge setzten Gehäuse bzw Schrank EN Configuring the PDM The Rittal PDM can be inserted directly into the preconfigured compartmen...

Страница 10: ...d in electro technics These persons are instructed by a skilled electrician in respect of the necessary protec tive equipment and safeguarding measures In addition they are instructed on the possible hazards of inappropriate behaviour and are trained for the particular work if necessary It is necessary for the person instructed in electro technics to take notice of and to understand the installati...

Страница 11: ...EMC environment Environnement CEM 1 EN 61439 1 8 1 PDR PDR PDR Schrankart Type of enclosure Type d armoire TS 8 Schrankhöhe Enclosure height Hauteur de l armoire 1200 2000 mm Breite Width Largeur ca approx 800 mm Tiefe Depth Profondeur ca approx 500 mm Gewicht Weight Poids ca approx 180 kg ohne Verpackung ohne Module without packaging without modules sans emballage sans modules Potenzialausgleich ...

Страница 12: ...TN C network 230 V 400 V 3 phase 250 A In this case a cross connector is applied at the infeed between N and PE model Wei dmüller WQV 70 2 model no 106350 9 2 PDM Functionality of the Rittal PDM mainly lies in power distribution within a data centre from the main distribution system at the PSM busbars to the racks or distribution of power from the PDR PSMs can be provided with 3 phase 400 230 V 16...

Страница 13: ... in the gland plate The floor must be flat and level for installa tion It must be sufficiently firm to ensure safe fastening of the enclosure to the floor e g with fastening plugs The enclosure must be connected firmly with the floor under all circumstances in order to prevent tilting Baying with TS 8 enclosures on the sides or at the rear is possible For information on baying installation and necessary...

Страница 14: ...g angle Installation in enclosure with 19 mounting angles The PDM is secured in its 19 compartment using the accessory screws Use of slide rails part no DK 7063 000 is recommended to brace the PDM housing If the infeed is connected via CEEkon plugs connection cable DK 7857 351 must be used The fuse indicated on the rating plate must be provided The infeed may only be plugged or unplugged when the ...

Страница 15: ... 3 1 10 3 Montage Einspeisung PDR 10 3 Installing the PDR infeed 10 3 Montage Alimentation PDR Ausschalten Switch off Désactivation 1 3 MD 4 Nm TX25 4 Bitte die Anleitung von ABB Tmax im Lieferumfang beachten Follow the instructions from ABB Tmax provided in the scope of delivery Veuillez respecter la notice d ABB Tmax fournie 4 6x M5 x 10 8x M6x16 SW8 ...

Страница 16: ...M Montageanleitung PDR PDM assembly instructions PDR PDM Notice de montage 1 2 EN F D 1 2 2 1 2 2 1 1 10 4 Montage PDM in PDR 10 4 Installing the PDM in the PDR 10 4 Montage PDM dans le PDR MD 4 Nm TX25 4x M6x16 ...

Страница 17: ...ed rack must be inspected for any electri cal equipment installed there that is engaged or any possible contact with parts under hazardous voltage Turning on the power without prior inspection may result in electric shock when working with connected electrical devices The infeed line must also be inspected for safe installation All master switches and automated circuit breakers of the plugged in P...

Страница 18: ...ncteur de protection doit pouvoir être identifiée à tout moment Prenez garde aux personnes se trouvant dans la zone de l instal lation électrique lorsque des équipements sont raccordés et alimentés 12 2 PDM Les fusibles déclenchés peuvent être réactivés en cours de fonctionnement Il convient de vérifier au préalable la raison pour laquelle le fusible s est déclenché La cause du déclen chement le cou...

Страница 19: ...cun liquide ou agent nettoyant agressif ne doit être utilisé L humidité ne doit en aucun cas péné trer dans l armoire afin d éviter toute corrosion ou tout choc électrique EN F D 15 Entsorgung 15 Disposal 15 Mise au rebut D Da die Rittal PDR und PDM hauptsächlich aus den Bestandteilen Stahl Kupfer und Kunststoff bestehen sind die Geräte für den Fall dass sie nicht mehr benötigt werden der Entsorgun...

Страница 20: ...ine et en Inde constituent les bases pour garantir un service après vente mondial rapide et efficace en s appuyant sur le réseau de toutes les filiales et agents Rittal à travers le monde Headquarter Deutschland Headquarters Germany Siège en Allemagne RITTAL GmbH Co KG Auf dem Stützelberg D 35745 Herborn Phone 49 0 2772 505 1855 Fax 49 0 2772 505 1850 E mail service rittal de Service HUB USA Servic...

Страница 21: ...21 PDR PDM Montageanleitung PDR PDM assembly instructions PDR PDM Notice de montage Notizen Notes ...

Страница 22: ...res Power Distribution Climate Control IT Infrastructure Software Services www rittal com contact You can find the contact details of all Rittal companies throughout the world here 09 2016 D 0000 00000647 Rev00 ...