background image

 

 

   

 

 

Operational Instruction 

  High voltage distribution boxes 6..10kV 

Type 07-5184-…./…. und 07-5185-….

/….

 

 

 

BARTEC 

Varnost d.o.o. 

Cesta 9.avgusta 59 

1410 Zagorje ob Savi 
Slovenia 

Tel.:  +386 59 221 471 

Fax:  +386 59 221 470 

[email protected] 

www.bartecvarnost.si 

Reservation

 

Technical data subject to change without notice. Changes, errors and 

misprints may not be used as a basis for any claim for damages. 

EN 1/4

 

 

 

 

 

 

 

 

 

 

Explosion protection 

 

 

 

 

ATEX 

Ex type of protection 

 II 2G Ex e IIC T6/T5 Gb  
 II 2D Ex tb IIIC T80°C/T95°C Db 

 

Certification 

IBExU13ATEX1001 
 

Environmental temperature range 

-20°C≤T

a

≤+55°C (T5 and EPDM Seal) 

-20°C≤T

a

≤+40°C (T6 and EPDM Seal) 

-30°C/-55°C≤T

a

≤+55°C (T5 and Silicone Seal) 

-30°C/-55°C≤T

a

≤+40°C (T6 and Silicone Seal) 

Approved for zones 

1 and 2 
21 and 22 
 

       

Technical data

 

Protection class 

(

EN 60529/IEC 60529) 

Stainless steel enclosures: 

Max.IP 66 – enclosure with lid 
Max IP 65 – enclosure with doors 

Polyester enclosures: 

Max.IP 66 
 

Seals 

 

Type 07-5H92 
EPDM 

 

- 20°C  to + 80°C 

Silicon                    - 55°C  to +100°C 
 
Type 07-5H95 
Silicon                   -30°C  to + 80°C 
Others                   -20°C  to + 80°C 

Mechanical strength 

Impact energy: 7 Joule (in accordance with 
standard EN 60079-0:2009) 

Enclosure material 

Stainless steel     Model 07-5H92 
Polyester black    Model 07-5H95 

Lid screws 

Stainless Steel, cross-head (+-) 

Recommended tightening torque 

M4 screw: ca. 1.2 Nm 
M6 screw: ca. 1.4 Nm 
 

Rated voltage 

Max.10000V 

 

Rated current 

Max.500A 

 

Conductor cross-section 

Max 300mm² 
 

Terminals 

A maximum of four certified supporting 
terminals can be integrated, having a 
maximum rated voltage of 10000V and 
a maximum rated connection capacity 
of 300mm² in accordance with the 
supplementary pages. 

 

Conduits 

When connecting wires and conduc-
tors to equipment in the increased 
safety protection class Ex-certified 
conduits must be used which are suit-
able for the respective wire and con-
ductor types. They must maintain 
protection type “e” and contain a suita-
ble sealant element such that, as a 
minimum, protection class IP54 of the 
connection enclosure in preserved.  
Drill holes for conduits not needed 
must be sealed using Ex-certified 
sealant plugs.  

 

 

  (

is

su

N

 A

 ( 

27

.0

1.

20

15

 
Note on instructions 

When working in hazardous areas, the safety of 
personnel  and  equipment  depends  on  compli-
ance  with  the  relevant  safety  regulations.  The 
people  in  charge  of  installation  and  mainte-
nance bear a special responsibility. It is essen-
tial  that  they  have  an  exact  knowledge  of  the 
applicable rules and regulations. 
The instructions provide a summary of the most 
important  safety  measures  and  must  be  read 
by  everyone  working  with  the  product  so  that 
they will be familiar with the correct handling of 
the product. 
The  instructions  have  to  be  kept  for  future 
reference and must be available throughout the 
expected life of the product. 
 

Description 

The connection enclosures 6... 10kV model 07-
5H9.-..../.... for use in potentially explosive 
atmosphere are made from Stainles Steel or 
from black Polyester. They are used to connect 
in-coming and out-going conductors near 
electrical equipment. Depending on the model, 
up to four live conductors are fed through the 
connection enclsure and connected on support-
ing terminals. Bartec Varnost connection enclo-
sures may be deployed in areas with potentially 
explosive atmospheres as defined in Zones1 
and 2 of the certified explosion sub-group II and 
temperature class T5/T6 and as well as in 
Zones 21 and 22 
The enclosures conform to the relevant standards 
EN 60079-0:2009, EN 60079-7:2007 and EN 
60079-31:2009 and were developed, produced 
and tested in accordance with ISO 9001:2008 and 
EN 60999. 

 

 

 

 

Отзывы: