Operational Instruction
High voltage distribution boxes 6..10kV
Type 07-5184-…./…. und 07-5185-….
/….
BARTEC
Varnost d.o.o.
Cesta 9.avgusta 59
1410 Zagorje ob Savi
Slovenia
Tel.: +386 59 221 471
Fax: +386 59 221 470
[email protected]
www.bartecvarnost.si
Reservation
Technical data subject to change without notice. Changes, errors and
misprints may not be used as a basis for any claim for damages.
EN 3/4
(is
su
e
N
o
A
/(
27
.0
1.
20
15
)
Take care when connecting conductors:
Always use suitable crimping tools when
crimping the wire-end ferrules to ensure a
consistent quality of pressing each time.
NOTICE! Take care not to damage
the individual wires.
Tighten all terminal points securely (in-
cluding those not in use).
Commissioning
Before commissioning, check that:
The device has been installed in compli-
ance with regulations.
The device is not damaged.
The connection has been established
properly.
The cables have been laid correctly.
All screws have been tightened securely.
The device functions perfectly.
Operation
Death or serious injury through improper
use.
The device may be operated only within
the technical limits that apply to it (see
page 1).
Maintenance and fault clearance
Risk of serious injury due to damaged parts.
If any part of the equipment is damaged, it
should be exchanged only with original
parts (e.g. sealing gasket/cable glands/
terminals).
Risk of serious injury due to incorrect
proceedings.
Only authorized qualified personnel are
allowed to do any of the work relating to
maintenance and fault clearance.
IEC/EN 60079-17 must be observed.
Do not open the enclosure when ener-
gized.
Maintenance
Risk of serious injury due to electrostatic
charging.
The operator of the enclosure must keep it in
good condition, monitor it and clean it regularly.
He has to determine the maintenance intervals
depending on the conditions of use.
Within the scope of maintenance:
Check enclosure, actuating elements,
cable entries, sealings, and cables regu-
larly for cracks and damage.
Make sure that they are properly estab-
lished.
Fault clearance
The device is defective if the encapsulation is
damaged and/or if one of the components does
not function any longer.
In this case:
Replace defective parts in the encapsula-
tion with original parts immediately.
Replace or repair the defective compo-
nents with original parts.
Note
Follow the components mounting instruc-
tions/operating instructions to replace or repair
the components.
Accessories, spare parts
For accessories and spare parts, see BARTEC
catalogue.
Disposal
Note
Ensure environmentally friendly disposal of all
components according to legal regulations.
The enclosures and its components contain
metal and plastic parts.
Therefore the statutory requirements for dispos-
ing of electronic scrap must be observed (e.g.
disposal by an approved disposal company).