Parameters and diagnostic messages
ID Px.
Parameters
Description
Specifies whether software limit position monitoring should be
activated.
0: inactive
1: active
Access
read/write
Update
effective immediately
4628
Software limit posi-
tions active
Unit
−
Specifies the limit value of the negative software limit position.
The value of the negative software limit position must be lower
than the value of the positive software limit position.
Access
read/write
Update
effective immediately
4629
Negative software
limit position
Unit
user defined
Specifies the limit value of the positive software limit position.
The value of the positive software limit position must be greater
than the value of the negative software limit position.
Access
read/write
Update
effective immediately
4630
Positive software limit
position
Unit
user defined
Specifies whether the automatic stop ramp should be activated
before exceeding the software limit position. (Automatic) brak-
ing is initiated as part of the error response. Braking is not initi-
ated if no error response is parameterised (warning).
0: inactive
1: active
Access
read/write
Update
effective immediately
4631
Activation of automat-
ic stop ramp software
limit position
Unit
−
Tab. 307 Parameters - Software limit position reached