6-10
l Tr o u b l e s h o o t i n g
Problem
E-Stop Press
Process High Temperature
–
If the process temperature
exceeds the process high tem-
perature setpoint, it shuts
down the dryer. Defaults are
set to 385°F {196°C} for
20 seconds.
Process Temperature Loop
Break
– If the process tem-
perature is outside of the oper-
ator entered deviation, alarm
band (see Process High
Temperature Deviation passive
alarm) and the process tem-
perature is not moving
towards the setpoint at a rate
greater than specified. It shuts
down the dryer. Defaults are
set at 3°F {3°C} over
20 seconds.
Possible cause
E-Stop button has been pressed in.
The process high temperature setpoint is
not at least 10°F {6°C} above the drying
setpoint.
One of the process solid state relays has
failed.
The air lines are restricted or loose.
The process setpoint is too low.
The process heater output on the control
board has failed.
Process RTD is loose or has fallen out.
The process heater has failed.
The air lines are restricted or loose.
The process blower is not running or is
running in the wrong direction.
The process heater output on the board
has failed or the output fuse has failed.
Process setpoint is too low.
Setback setpoint is too low.
Solution
Release E-Stop.
Reset the process high temperature
setpoint at least 10°F {6°C} above the
drying setpoint.
Replace the solid state relay.
Straighten any crimps in the hoses.
Tighten any loose hoses.
Set the process setpoint higher or install
an optional precooler.
Replace the control board.
Check the process RTD and tighten if
needed.
Check the heater fuses, and resistance
across each leg of the process heater.
Straighten any crimps in the hoses.
Tighten any loose hoses.
Correct the cause of the non-running
blower (blown fuse, etc.) or reverse the
rotation of the blower.
Replace the board or the fuse for the
output.
Adjust the setpoint or add a precooler.
Adjust the setpoint or add a precooler.
Shutdown Alarms
If an alarm occurs, a red dialog box is displayed on the dryer’s touch screen
control. The dryer will shut down automatically during a to prevent damage
to the equipment or personnel. The dialog box will indicate whether the
alarm is a shut down alarm or a passive alarm.
Содержание HTC 120
Страница 10: ...viii l Table of Contents ...
Страница 30: ...2 14 l Description ...
Страница 35: ...Installation General Installation General l 3 5 3 I n s t a l l a t i o n ...
Страница 65: ...Installation Hard Piping Kits Installation Piping Hoses l 3 35 3 I n s t a l l a t i o n ...
Страница 80: ...3 50 l Installation Piping Hoses ...
Страница 81: ...3 I n s t a l l a t i o n Installation Main Power Connections Installation Main Power Connections l 3 51 ...
Страница 88: ...3 58 l Installation Piping Hoses ...
Страница 89: ...3 I n s t a l l a t i o n Installation Main Power Connections l 3 59 Installation Conveying Lines ...
Страница 92: ...3 62 l Installation Conveying Lines ...
Страница 93: ...Installation Water Lines 3 I n s t a l l a t i o n Installation Water Lines l 3 63 ...
Страница 115: ...Installation Compressed Air Lines 3 I n s t a l l a t i o n Installation Compressed Air Lines l 3 85 ...
Страница 124: ...3 94 l Installation Gas Piping and Exhaust Flue ...
Страница 125: ...Installation Testing 3 I n s t a l l a t i o n Installation Testing l 3 95 ...
Страница 149: ...4 O p e r a t i o n Operation l 4 7 Control Function Flow Charts continued Operation Flow Chart 1 1A 2 3 4 continued 5 ...
Страница 152: ...Control Function Flow Charts continued Setup Flow Chart 1 1B 19 38 20 34 37 4 10 l Operation continued ...
Страница 250: ...4 108 l Operation ...
Страница 286: ...5 36 l Maintenance ...