12 - 5
Fault Finding
Procedures that require charging or discharging the system are not given in this manual as they require special equipment that
is usually held only by trained refrigeration engineers. Fault indications are given in the table below.
The system will not function in very low ambient temperatures, therefore tests should be carried out in a warm environment.
It is recommended that, to locate faults on the system accurately and quickly, an electronic leak detector and a refrigerant
pressure gauge should be used. However, leaks can be detected on the system by using soapy water applied to the suspected
leak area and system pressure can be assessed by the state of refrigerant passing through the receiver drier sight glass.
Following sections of the manual deal with the major components of the air conditioning system and give further fault finding
and maintenance information.
General Fault Indications
There are several indications that may help to determine the fault area on a system not working efficiently:
a)
Poor performance
Low system pressure -
Evacuate and recharge system.
Condenser coil air flow restricted -
Remove debris from around coil using
compressed air or low pressure water.
Air filters blocked
Clean with detergent and water.
Compressor drive belt too slack
Adjust to correct tension.
b)
Warm or slightly cool air
Expansion valve stuck open or closed -
Renew expansion valve.
emitted from unit
c)
Blower does not operate
Fuse blown
Replace fuse (20A) and retest.
Circuit fault
Fault find and repair.
d)
Compressor clutch
Condenser coil blockage -
Remove debris from around coil/renew condenser.
continually cuts out
Overcharging of refrigerant system-
Evacuate and recharge system.
Blocked expansion valve/condenser -
Clear blocked component .
Sight Glass Indications
An approximate indication of the condition of the refrigerant can be seen through the receiver/drier sight glass when the
compressor is running. Refer also to
Checking Refrigerant Charge Level
, on page 12-8.
Clear - No fault indicated unless the system is unable to provide cool air. The indication then is that
the system is completely discharged of refrigerant.
Foam or bubbles - Refrigerant low and in need of charging.
Clouded - Desiccant breakdown in the receiver-drier.
Note
: Sight glass indications cannot always give a positive identification of a problem. Further diagnosis, preferably by a
refrigeration engineer using pressure gauges, is advisable before reaching a definite conclusion.
Section B
Body & Framework
9803/6410
Section B
12 - 5
Issue 1
Air Conditioning
S201520C
S201520A
S201520B
Summary of Contents for JS130
Page 65: ...Section 3 Section 3 9803 6410 Issue 1 9 1 9 1 Routine Maintenance Component Location Diagram...
Page 118: ......
Page 119: ...3 1 Section C Electrics 9803 6410 Section C 3 1 Issue 1 Layout Operator s Cab...
Page 142: ...5 3 Section C Electrics 9803 6410 Section C 5 3 Issue 1 Pump Control FLOW CHART...
Page 207: ......
Page 209: ......
Page 210: ...3 4 Section E Hydraulics 9803 6410 Section E 3 4 Issue 2 Schematics Shuttle Block...
Page 532: ...Contents Page No Technical Data 1 1 i Engine 9803 6410 i Issue 1 Section K Section K...