76
Commissioning
Type 8098 FLOWave L
17.
With the Bürkert Communicator software, print a pdf report of the new settings of the device.
18. Select the process values that you want to save and export the selected data under the format
(*.edipdb). Refer to the Type 8920 Operating Instruction.
19.
Disconnect the Bürkert Communicator software from the device.
9.4
First commissioning for detecting a change of liquid
in the pipe
1.
Energise the device.
2. Connect the device to the Bürkert Communicator software. Print a pdf report of all the current settings
of the device. Select the process values that you want to monitor graphically. Refer to the Type 8920
Bürkert Communicator software from
.
3. On the display module, do the settings of the
Quick start
menu. Refer to chapter 11.2
.
4. If the liquid is not water, then read out the value of the
Acoustic transmission factor
. Refer to
chapter 15.13
•
If the value is higher than 20 % ±5 %, then the flow rate of the liquid can be measured by the device.
•
If the value is lower than 20 % ±5 %, then the flow rate of the
liquid might not be measured accurately by
the device.
5.
If the liquid is not water, then read out the value of the
DF
. Refer to chapter 15.12.
•
If the value is between 0.8 and 1.2, then the flow rate of the liquid can be measured by the device.
•
If the value is lower than 0.8 or higher than 1.2, then the flow rate of the liquid might not be measured
accurately by the device.
6.
Adjust the parameter
Damping
of the acoustic transmission factor, depending on your application. Refer
to chapter 15.13.3
7.
Adjust the parameter
Damping
of the DF, depending on your application. Refer to chapter 15.12.3
or
.
8. Check the correct behaviour of the device by using the menu
Simulation
. Refer to chapter 17.27
9. With the Bürkert Communicator software, print a pdf report of the new settings of the device.
10. Select the process values that you want to save and export the selected data under the format
(*.edipdb). Refer to the Type 8920 Operating Instruction.
11.
Disconnect the Bürkert Communicator software from the device.
English
Summary of Contents for Flowave 8098
Page 4: ...General contents 4 Type 8098 FLOWave L English...
Page 12: ...12 Type 8098 FLOWave L English...
Page 36: ...36 Technical data Type 8098 FLOWave L English...
Page 72: ...72 Type 8098 FLOWave L English...
Page 78: ...78 Commissioning Type 8098 FLOWave L English...
Page 96: ...96 Type 8098 FLOWave L English...
Page 144: ...144 Type 8098 FLOWave L English...
Page 248: ...248 Type 8098 FLOWave L English...
Page 286: ...286 SAW sensor Maintenance Type 8098 FLOWave L English...
Page 304: ...304 Type 8098 FLOWave L English...
Page 316: ...316 Type 8098 FLOWave L English...
Page 350: ...350 Spare parts and accessories Type 8098 FLOWave L English...
Page 352: ...352 Appendix Type 8098 FLOWave L English...
Page 353: ......
Page 354: ...www burkert com...