58
Electrical installation
Type 8098 FLOWave L
8.7
Specifications of the conductors for the 12 push-in
terminal strip
Table 16:
Specifications of the conductors for the terminal strip
Specification of the conductors
Recommended value range
Cross section of a solid conductor H05(07) V-U
0.25...1.5 mm
2
Cross section of a stranded conductor H05(07) V-K,
with a wire ferrule but without collar
0.25...1.5 mm
2
Cross section of a stranded conductor H05(07) V-K,
with a wire ferrule with a plastic collar
0.25...0.75 mm
2
Cross section of other kinds of conductors
0.2...1.5 mm
2
(AWG24...AWG16)
8.8
Terminal assignment of the 12 push-in terminal strip
The terminal strip located in the transmitter housing has 12 push-in terminals.
→
To access the 12 push-in terminal strip, open the front of the transmitter; see chapter
Fig. 24:
Wiring ex works of the 12 push-in terminal strip
→
If you need to disconnect a conductor, first push the terminal with a slot screwdriver 3.0 mm (any length)
and a force of max. 40 N.
1 2 3 4 5 6 7 8 9 1 1 12
1
0
Green LED
Orange LED
(device variant with two M20x1.5 cable glands)
•
Green LED:
− flashes slowly if the operation of the device is correct.
− flashes quickly if there is a communication problem with the measurement board.
•
Orange LED lit if the related digital output is switched to ON (device variant with two M20x1.5 cable glands)
•
Terminal 1: GND (blue conductor, factory wired, internally connected to the 5-pin M12 male connector)
•
Terminal 2: CAN_L (grey conductor, factory wired, internally connected to the 5-pin M12 male connector)
•
Terminal 3: CAN_shield (brown conductor, factory wired, internally connected to the 5-pin M12 male
connector)
•
Terminal 4: CAN_H (black conductor, factory wired, internally connected to the 5-pin M12 male connector)
•
Terminal 5: 12...35 V DC (white conductor, factory wired, internally connected to the 5-pin M12 male
connector)
English
Summary of Contents for Flowave 8098
Page 4: ...General contents 4 Type 8098 FLOWave L English...
Page 12: ...12 Type 8098 FLOWave L English...
Page 36: ...36 Technical data Type 8098 FLOWave L English...
Page 72: ...72 Type 8098 FLOWave L English...
Page 78: ...78 Commissioning Type 8098 FLOWave L English...
Page 96: ...96 Type 8098 FLOWave L English...
Page 144: ...144 Type 8098 FLOWave L English...
Page 248: ...248 Type 8098 FLOWave L English...
Page 286: ...286 SAW sensor Maintenance Type 8098 FLOWave L English...
Page 304: ...304 Type 8098 FLOWave L English...
Page 316: ...316 Type 8098 FLOWave L English...
Page 350: ...350 Spare parts and accessories Type 8098 FLOWave L English...
Page 352: ...352 Appendix Type 8098 FLOWave L English...
Page 353: ......
Page 354: ...www burkert com...