188
SAW sensor – Parameter
Type 8098 FLOWave L
None
damping: all
the fluctuations of the
measured values are
transmitted
Low
damping
Medium
damping
High
damping
Chosen damping level is applied
No damping if 2 consecutive measured values vary for ±30 %
Fig. 59:
Operation of the available damping levels
Table 28:
Response times (10 %...90 %) of the damping levels for the liquid velocity measurements
Damping level
Response time which is associated with the damping level
chosen for the volume flow plus...
None
•
5 s if the
Refresh time
is set to
Long
•
< 0.5 s if the
Refresh time
is set to
Short
or
Very short.
Low
...1 s
Medium
...10 s
High
...30 s
Special
...User-defined
Response time
: see chapter 15.8.3
To set a predefined damping level of the measured liquid velocity values, do the following:
→
Go to the
CONFIGURATION
view.
→
SAW sensor
→
Confirm to access the
Parameter
view.
→
Stand. meas. values
→
Liquid velocity
→
Damping
The
Current settings
are displayed
→
Choose a damping level between
Low
,
Medium
and
High
The
New settings
are
displayed.
→
Save.
The damping of the liquid velocity values is active and a predefined damping level is chosen.
English
Summary of Contents for Flowave 8098
Page 4: ...General contents 4 Type 8098 FLOWave L English...
Page 12: ...12 Type 8098 FLOWave L English...
Page 36: ...36 Technical data Type 8098 FLOWave L English...
Page 72: ...72 Type 8098 FLOWave L English...
Page 78: ...78 Commissioning Type 8098 FLOWave L English...
Page 96: ...96 Type 8098 FLOWave L English...
Page 144: ...144 Type 8098 FLOWave L English...
Page 248: ...248 Type 8098 FLOWave L English...
Page 286: ...286 SAW sensor Maintenance Type 8098 FLOWave L English...
Page 304: ...304 Type 8098 FLOWave L English...
Page 316: ...316 Type 8098 FLOWave L English...
Page 350: ...350 Spare parts and accessories Type 8098 FLOWave L English...
Page 352: ...352 Appendix Type 8098 FLOWave L English...
Page 353: ......
Page 354: ...www burkert com...