292
Outputs – Parameter
Type 8098 FLOWave L
18.4
Disabling an analogue output
If an analogue output is not wired, the analogue output can be disabled to avoid the generation of the
events
Output 1, open loop
or
Output 3, open loop
.
To disable an analogue output, do the following:
→
Go to the
CONFIGURATION
view.
→
Outputs
→
Confirm to access the
Parameter
view.
→
Output 1 type
or
Output 3 type
→
Disabled
→
Save.
The analogue output is disabled.
The menus related to the analogue output are not displayed any more.
18.5
Setting the parameters of a digital output
By default, the device has 1 digital output,
Output 2:digital
, that is configured as a pulse output.
The output 3 can also be configured as a digital output: see chapter 18.2
.
A digital output can be configured:
•
as an on/off output,
• or, to switch depending on two threshold values,
• or, as a frequency output,
• or, as a pulse output.
Table 44:
Default parameters of the digital output
Parameter
Default value
DN of process connections
Mode
Pulse
all the diameters
Max. pulse time
65 ms
all the diameters
Max. frequency
2000 Hz
all the diameters
Pulse mode
Pulses/volume
all the diameters
English
Summary of Contents for Flowave 8098
Page 4: ...General contents 4 Type 8098 FLOWave L English...
Page 12: ...12 Type 8098 FLOWave L English...
Page 36: ...36 Technical data Type 8098 FLOWave L English...
Page 72: ...72 Type 8098 FLOWave L English...
Page 78: ...78 Commissioning Type 8098 FLOWave L English...
Page 96: ...96 Type 8098 FLOWave L English...
Page 144: ...144 Type 8098 FLOWave L English...
Page 248: ...248 Type 8098 FLOWave L English...
Page 286: ...286 SAW sensor Maintenance Type 8098 FLOWave L English...
Page 304: ...304 Type 8098 FLOWave L English...
Page 316: ...316 Type 8098 FLOWave L English...
Page 350: ...350 Spare parts and accessories Type 8098 FLOWave L English...
Page 352: ...352 Appendix Type 8098 FLOWave L English...
Page 353: ......
Page 354: ...www burkert com...