303
Outputs – Maintenance
Type 8098 FLOWave L
20.7
Checking the correct operation of a pulse output
To check the correct operation of a digital output configured as a pulse output, do the following:
→
Connect a counter to the digital output configured as a pulse output.
→
Energize the output.
→
Go to the
CONFIGURATION
view.
→
Outputs
→
Confirm to access the
Parameter
view.
→
Go to the
MAINTENANCE
view.
→
Output 2: digital
or
Output 3: digital
, configured as a pulse output
→
Test
→
Enter a frequency value
→
Enter a number of pulses
Check if the output is operating correctly. For example
through the correct flashing of the related LED on the transmitter board.
→
To test another number of pulses or
To stop the test and go back to the parent menu.