342
Maintenance and troubleshooting
Type 8098 FLOWave L
24.12.3
Message "Not totally filled"
Message
Not totally filled
Symbol displayed in the
information bar
Depends on the device status the event is associated to.
Possible cause
The calibration has failed. The calibration has failed because of one of the
possible causes:
• The sensor may be broken (valid for product variants with DN08).
•
The tube is not totally filled. Thus not all the sensors are in contact with
the liquid and measurement is not possible.
The related event must be enabled. See chapter 15.14 Diagnostics: moni
toring special events that occur in the process, on the sensor or on the
What to do?
→
Make sure the measurement tube is completely filled, for example by
increasing the flow rate.
→
If the message
No signals from interdigital transducer
is generated
simutaneously, then send the product back to Bürkert.
→
If the message
Not totally filled
remains, then send the product back to
Bürkert.
24.12.4
Message "Liquid out of range"
Message
Liquid out of range
Symbol displayed in the
information bar
Depends on the device status the event is associated to.
Possible cause
The speed of sound in the liquid is out of range.
The related event must be enabled. See chapter 15.14 Diagnostics: moni
toring special events that occur in the process, on the sensor or on the
electronics.
The density in the liquid is out of range.
What to do?
→
Make sure the liquid in the pipe meets the technical specifications given
in the data sheet for the device and in chapter 6 Technical data
.
24.12.5
Message "Unstable flow rate"
Message
Unstable flow rate
Symbol displayed in the
information bar
Depends on the device status the event is associated to.
Possible cause
The flow rate is not stable. The standard deviation of the flow rate measure
-
ments is too high.
The related event must be enabled. See chapter 15.14 Diagnostics: moni
toring special events that occur in the process, on the sensor or on the
What to do?
→
Make sure the operation of the equipment in the process, such as
pumps and process valves, is correct.
English
Summary of Contents for Flowave 8098
Page 4: ...General contents 4 Type 8098 FLOWave L English...
Page 12: ...12 Type 8098 FLOWave L English...
Page 36: ...36 Technical data Type 8098 FLOWave L English...
Page 72: ...72 Type 8098 FLOWave L English...
Page 78: ...78 Commissioning Type 8098 FLOWave L English...
Page 96: ...96 Type 8098 FLOWave L English...
Page 144: ...144 Type 8098 FLOWave L English...
Page 248: ...248 Type 8098 FLOWave L English...
Page 286: ...286 SAW sensor Maintenance Type 8098 FLOWave L English...
Page 304: ...304 Type 8098 FLOWave L English...
Page 316: ...316 Type 8098 FLOWave L English...
Page 350: ...350 Spare parts and accessories Type 8098 FLOWave L English...
Page 352: ...352 Appendix Type 8098 FLOWave L English...
Page 353: ......
Page 354: ...www burkert com...