155
SAW sensor – Parameter
Type 8098 FLOWave L
increasing
monitored
value
decreasing
monitored
value
A:
Error low
D:
Error high
C:
Warning high
B:
Warning low
A
B
C
D
1
2a
2b
3a
3b
h
h
h
h
C
D
1
2b
3b
2a
3a
A
B
2b
3b
1
2a
3a
h: value of the hysteresis. An hys-
teresis value that is equal to 0
means that the device reacts as
soon as a limit is reached.
A: low error limit (
Error low
)
B: low warning limit (
Warning low
)
C: high warning limit (
Warning high
)
D: high error limit (
Error high
)
1: normal range of the monitored value
2a: lower warning range of the
monitored value
3a: lower error range of the moni-
tored value
2b: upper warning range of the
monitored value
3b: upper error range of the moni-
tored value
Monitored
value is in the
Colour of the device status indicator
and generated message
Condition
Error range
Red
1)
indicator,
Failure
message
•
if the monitored value was in the LOWER
warning range and the LOW ERROR value is
reached.
• if the monitored value was in the UPPER
warning range and the HIGH ERROR value is
reached.
Warning range
Yellow
1)
indicator,
Out of specification
message
•
if the monitored value was in the LOWER error
range and the LOW ERROR value + the HYS
-
TERESIS value is reached.
• if the monitored value was in the normal range
and the HIGH WARNING value is reached.
• if the monitored value was in the UPPER error
range and the HIGH ERROR value minus the
HYSTERESIS value is reached.
• if the monitored value was in the normal range
and the LOW WARNING value is reached.
Normal range
• White
1)
indicator, no message, if
the
Diagnostics
in the menu
SAW
sensor
–
Parameter
is inactive
(default setting).
• or green
1)
indicator, no message, if
the
Diagnostics
in the menu
General
settings
–
DIAGNOSTICS
are active.
•
if the monitored value was in the LOWER
warning range and the LOW WARNING value +
the HYSTERESIS value is reached.
• if the monitored value was in the UPPER
WARNING range and the HIGH WARNING
value minus the HYSTERESIS value is reached.
Fig. 52:
Operating principle of the monitoring with an hysteresis
1)
If the operating mode of the device status indicator is set to NAMUR. See chapter 12.4
English
Summary of Contents for Flowave 8098
Page 4: ...General contents 4 Type 8098 FLOWave L English...
Page 12: ...12 Type 8098 FLOWave L English...
Page 36: ...36 Technical data Type 8098 FLOWave L English...
Page 72: ...72 Type 8098 FLOWave L English...
Page 78: ...78 Commissioning Type 8098 FLOWave L English...
Page 96: ...96 Type 8098 FLOWave L English...
Page 144: ...144 Type 8098 FLOWave L English...
Page 248: ...248 Type 8098 FLOWave L English...
Page 286: ...286 SAW sensor Maintenance Type 8098 FLOWave L English...
Page 304: ...304 Type 8098 FLOWave L English...
Page 316: ...316 Type 8098 FLOWave L English...
Page 350: ...350 Spare parts and accessories Type 8098 FLOWave L English...
Page 352: ...352 Appendix Type 8098 FLOWave L English...
Page 353: ......
Page 354: ...www burkert com...